OSHA Accident Investigation · Summary #14548762
BURN,RECEPTACLE,ELECTRICAL,E GI VII,GROUND FAULT,ELECTRIC SHOCK,ELEC EQUIPMENT--MISC
Event description
ELECTRIC SHOCK & BURN - GROUND FAULT IN RECEPTACLE OUTLET
Investigation abstract
AN EMPLOYEE WAS PERFORMING HIS WEEKLY DUTY OF SCRUBBING A WET CONCRETE FLOOR WIT H A 120-VOLT TORNADO FLOOR CLEANING MACHINE (MODEL 283). THE EMPLOYEE RECEIVED A N ELECTRIC SHOCK WHEN HE HELD THE HANDLE OF THE MACHINE. THE ELECTRIC SHOCK CAUS ED FIRST DEGREE BURNS, AND THE EMPLOYEE WAS HOSPITALIZED FOR HIS INJURIES. ON IN SPECTION, THE RECEPTACLE OUTLET BEING USED TO SUPPLY THE MACHINE WITH ELECTRIC P OWER WAS FOUND TO BE WIRED FOR 240 VOLTS, AND THE GROUNDING CONDUCTOR FOR THE OU TLET WAS FOUND TO HAVE 120 VOLTS IMPRESSED ON IT.
Victim
-
#1 Hospitalized Age 34 M
- Nature of injury
- 10
- Part of body
- 3
- Event type
- 13
- Source
- 15
- Occupation code
- 999
- Human factor
- 14
- Environmental factor
- 18
- Task assigned
- 1