104,543Records 70,659Employers 84,666Hospitalizations 27,563Amputations 2015-01-01 2025-09-30
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #14567804

FIREFIGHTER,SERVICE CONDUCTOR,ELECTRICAL,E GI VII,FIRE,ELECTRIC METER,GROUND FAULT,ELECTRIC SHOCK

Event
FIREFIGHTER,SERVICE CONDUCTOR,ELECTRICAL,E GI VII,FIRE,ELECTRIC METER,GROUND FAULT,ELECTRIC SHOCK
Linked inspection
No inspection record linked to this accident's victims.
Summary number
14567804
Report ID
454520

Event description

ELECTRIC SHOCK - GROUND FAULT AT ELECTRIC METER

Investigation abstract

WHILE FIGHTING A TRAILER FIRE, TWO FIREMEN WERE RECEIVING ELECTRIC SHOCKS EVEN T HOUGH THE ELECTRIC METER HAD BEEN PULLED AND THOUGH THE FIREMEN WERE WEARING FUL L TURNOUT GEAR. THE ELECTRIC UTILITY WAS CALLED, AND THE ELECTRIC SERVICE WAS DI SCONNECTED AT THE TRANSFORMER POLE. THE NEUTRAL AND PHASE CONDUCTORS HAD BEEN FU SED TOGETHER, WHICH CAUSED THE RELATIVE VOLTAGE ON THE NEUTRAL TO RISE. THIS IN TURN HAD ENERGIZED THE METER BASE.

Victims (2)

  1. #1 Hospitalized Age 20 M

    Nature of injury
    10
    Part of body
    19
    Event type
    13
    Source
    15
    Occupation code
    417
    Human factor
    4
    Environmental factor
    17
    Hazardous substance
    8870
    Task assigned
    1
  2. #2 Hospitalized Age 19 M

    Nature of injury
    10
    Part of body
    19
    Event type
    13
    Source
    15
    Occupation code
    417
    Human factor
    4
    Environmental factor
    17
    Hazardous substance
    8870
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.