Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #221422827

COLT SERVICES, LP

Event
Burn, Explosion, Flange, Flying Object, Fracture, Gas Leak, Hot Work, Leak, Leg, Multi-employer Worksite, Multiemployer, Naphtha, PPE, Process Safety, Refinery, Skin, Struck By
NAICS
213112
Inspection type
Referral
Activity number
#345703466
Employer profile
COLT SERVICES, LP
Summary number
221422827
Report ID
0626600

Event description

Employee suffers burns and fracture in explosion at refinery

Investigation abstract

An employee was working for a contractor that supported gas and oil operations. replaced so that workers could install a wire wrap and seal the leak. The replacement bolts were longer and had injection collars. Workers would do the wire wrap and inject the bolts with a sealant to stop the leak. At 1:00 a.m. on December 23, 2021, an employee was working for the contracting firm that would remove and replace the bolts, while the other contractor assisted. As the employee was waiting for the other contractor, an explosion occurred during the repair. The employee suffered second-degree burns. In addition, he suffered a fractured femur when he was struck by a flying object from the explosion. He was hospitalized. Another worker there was not hospitalized. The employee's supervisors knew that the flange had auto ignited the day before they were On or before December 21, 2021, a leak was found on a flange for a bypass line called to come and fix the leak. The supervisors did not, though, ensure that employees had upgraded their personal protective equipment (PPE) to reduce the risk of serious injuries should a flash fire reoccur. They did not evaluate the hazards and select and require the use of appropriate PPE using their knowledge of the operating conditions, nor did they use refinery owner's safe work practice requirement of using upgraded PPE when work activity is going to be done in areas with potential flash fire. on the Hydro Desulfurization Unit (HDU-1) at refinery operated by an international oil company. The leak was detected because the leak had auto ignited. The refinery owner's fire team had been called out to put the fire out. After the fire was out, steam lances were continuously directed on the flange due to the potential of another flash fire from the leaking heated naphtha. The refinery's owner hired two contract companies to repair the leaking flange using a method called hot bolting. In this method, one bolt at a time was removed and

Victim

  1. #1 Hospitalized Age 30 M

    Event type
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.