OSHA Accident Investigation · Summary #570887

E GI IV,ELECTRICAL,ELECTROCUTED,ELECTRICAL WORK,INTERLOCK,LOCKOUT,ELECTRICAL BOX,UNTRAINED

Event
E GI IV,ELECTRICAL,ELECTROCUTED,ELECTRICAL WORK,INTERLOCK,LOCKOUT,ELECTRICAL BOX,UNTRAINED
Linked inspection
No inspection record linked to this accident's victims.
Summary number
570887
Report ID
523400

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

AN EMPLOYEE HAD BEEN WORKING ON A PROBLEM WITH HIS BRASS DIE CASTING MACHINE. TH COULD NOT HAVE FOUND THIS PROBLEM, SINCE HE WAS A DIE CASTER AND A LEAD MAN, NOT AN ELECTRICIAN. THE CAUSE OF DEATH WAS DETERMINED TO BE ELECTRIC SHOCK, THOUGH THE EXACT POINTS OF CONTACT WITH THE MACHINE COULD NOT BE DETERMINED. BURN MARKS WERE FOUND ON BOTH THE EMPLOYEE'S PALMS. E EMPLOYEE WAS FOUND LYING DEAD ON THE FLOOR IN FRONT OF THE MAIN ELECTRICAL CON TROL PANEL, WITH ITS DOOR OPEN. THE PANEL CONTAINED CIRCUIT PARTS ENERGIZED AT 2 40/480 VOLTS, 3 PHASE. THE INTERLOCK HANDLE ON THE DOOR HAD BEEN REMOVED, PERMIT TING THE CIRCUIT PARTS TO REMAIN ENERGIZED WHEN THE PANEL DOOR WAS OPEN. ALTHOUG H THERE WERE NO WITNESSES TO THE ACCIDENT, THE EMPLOYEE HAD BEEN SEEN A HALF HOU R EARLIER PUSHING BUTTONS AND WIGGLING CONDUCTORS IN ANOTHER SMALLER CONTROL BOX NEAR THE DIE AREA. THE EMPLOYEE, HOWEVER, HAD NOT EXPLAINED WHAT HE WAS DOING. AFTER THE ACCIDENT, A DEFECTIVE RELAY WAS FOUND. THE DECEASED EMPLOYEE PROBABLY

Victim

  1. #1 Fatality Age 27 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    719
    Human factor
    1
    Environmental factor
    18
    Task assigned
    1