Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #601468

FLORIDA POWER CORPORATION

Event
ELEC PROTECT EQUIP, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, TRANSFORMER
NAICS
000000
Inspection type
Accident-driven
Activity number
#106313588
Employer profile
FLORIDA POWER CORPORATION
Summary number
601468
Report ID
420600

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

A TWO-PERSON UNDERGROUND RESIDENTIAL DISTRIBUTION CREW FOR AN ELECTRIC UTILITY A TO THE RIGHT SIDE. AS HE WAS MANEUVERING THE CONDUCTOR INTO POSITION, HE LEANED OR FELL FORWARD, AND HIS CHEST CONTACTED THE TOP 120-VOLT BUSBAR AS HIS LEFT AR M CONTACTED A GROUND WIRE ABOVE HIS INSULATED GLOVE. THE EMPLOYEE WAS ELECTROCUT ED. RRIVED AT A RESIDENTIAL AREA TO CONNECT UNDERGROUND WIRING FROM A PAD-MOUNTED TR ANSFORMER TO A PEDESTAL THEY WERE GOING TO INSTALL NEAR TWO NEWLY BUILT HOMES. O NE OF THE TWO EMPLOYEES, AN APPRENTICE POWER LINE WORKER, MADE THE CONNECTIONS O N THE PEDESTAL. HIS COWORKER, A JOURNEYMAN LINE WORKER, CHECKED OVER THE WORK, T HEN TOLD THE APPRENTICE THAT HE WAS GOING TO CONNECT THE INSTALLATION TO THE ENE RGIZED TRANSFORMER. THE JOURNEYMAN WENT TO THE PAD-MOUNTED TRANSFORMER, PUT ON E LBOW-LENGTH RUBBER INSULATING GLOVES, AND KNELT IN FRONT OF THE TRANSFORMER. HE THEN STARTED TO FEED THE NEUTRAL CONDUCTOR FROM THE LEFT SIDE OF THE TRANSFORMER

Victim

  1. #1 Fatality Age 29 M

    Nature of injury
    10
    Part of body
    5
    Event type
    13
    Source
    15
    Occupation code
    577
    Human factor
    1
    Environmental factor
    18
    Hazardous substance
    8870
    Task assigned
    1