OSHA Accident Investigation · Summary #673590
FURNACE,LEAK,MAINTENANCE,FLAMMABLE VAPORS,WORK RULES,EXPLOSION,GAS LEAK,UNTRAINED
Event description
GAS EXPLOSION IN REFORMER FURNACE
Investigation abstract
EMPLOYEES #1 THROUGH #6 WERE PREPARING A LARGE REFORMER FURNACE FOR FIRING UP. T HE FURNACE HAD BEEN SHUT DOWN FOR ABOUT 5 MONTHS. BECAUSE THERE WAS A LACK OF CO MMUNICATION BETWEEN THE WORKERS, AND BECAUSE SOME OF THE EMPLOYEES WERE NOT FAMI LIAR WITH THE FURNACE OPERATOR'S MANUAL, THE FURNACE WAS LIT WHILE 10 MANUALLY O PERATED GAS VALVES WERE OPEN. THE FLAME IGNITED THE GAS WHICH HAD BUILT UP IN TH E FURNACE, CAUSING AN EXPLOSION. THE PROPER PROCEDURE IS TO OPEN THE VALVE ON EA CH BURNER, AND LIGHT EACH BURNER, SEPARATELY. ALSO, A FIVE MINUTE PRESSURE TEST IS CALLED FOR TO DETECT ANY LEAKS IN THE SYSTEM. THE EXPLOSION PROBABLY WOULD HA VE BEEN PREVENTED IF THE PRESSURE TEST HAD BEEN RUN.