105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #674952

BURN,CLOTHING,ELECTRIC ARC,E GI III,ELECTRICAL,ELECTRICIAN,ELECTRICAL WORK,LOCKOUT,ELECTRICAL BOX,ELECTRICAL FAULT

Event
BURN,CLOTHING,ELECTRIC ARC,E GI III,ELECTRICAL,ELECTRICIAN,ELECTRICAL WORK,LOCKOUT,ELECTRICAL BOX,ELECTRICAL FAULT
Linked inspection
No inspection record linked to this accident's victims.
Summary number
674952
Report ID
454510

Event description

BURN - ELECTRICAL FAULT IN ELECTRICAL BOX

Investigation abstract

THE PLANT ELECTRICIAN FOR A MANUFACTURING PLANT WAS CONNECTING POWER TO A ROYAL ED FIRST AND SECOND DEGREE BURNS TO HIS FACE AND LEFT ARM. HE WAS HOSPITALIZED F OR HIS INJURIES. MASTER ROLL GRINDER AT A BUS DUCT DISCONNECT BOX. THE DISCONNECT BOX WAS CONNECT ED TO A 600-VOLT BUS 12 FEET ABOVE THE FLOOR. ALL THE WIRING AND CONDUIT HAD BEE N INSTALLED EXCEPT FOR THE WIRING GOING INTO THE DISCONNECT BOX. A WATER PIPE HA D BEEN INSTALLED IN FRONT OF THE DOOR OF THE BOX SO THAT ITS DOOR COULD OPEN ONL Y UP TO A 45 DEGREE ANGLE. THE DISCONNECT WAS IN THE OFF POSITION, AND ALL FUSES HAD BEEN REMOVED. THE ELECTRICIAN WAS STANDING ON AN ELEVATED POWER LIFT INSTAL LING THE GROUNDING CONDUCTOR TO ITS CONNECTION IN THE BOX WHEN AN ELECTRICAL EXP LOSION OCCURRED. THE ELECTRICIAN HAD APPARENTLY CAUSED A GROUND FAULT. HE RECEIV

Victim

  1. #1 Hospitalized Age 42 M

    Nature of injury
    5
    Part of body
    9
    Event type
    14
    Source
    15
    Occupation code
    575
    Human factor
    10
    Environmental factor
    18
    Hazardous substance
    8880
    Task assigned
    1