OSHA Accident Investigation · Summary #704973
ELEC PROTECT EQUIP,OVERHEAD POWER LINE,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,E PTD,ELEC UTILITY WORK,AERIAL LIFT
Event description
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE
Investigation abstract
TWO LINEMEN WERE WORKING IN AN AERIAL LIFT RESTORING POWER TO A RESIDENTIAL AREA . THE LEAD LINE MECHANIC FOUND THE PROBLEM TO BE A DEFECTIVE FUSE HOLDER. ONE OF THE EMPLOYEES LOWERED THE AERIAL LIFT DOWN TO THE TOP OF THE SERVICE TRUCK TO G ET A REPLACEMENT FUSE HOLDER. HE THEN RAISED THE AERIAL LIFT BACK UP TO THE OVER HEAD LINE AND REPLACED THE DEFECTIVE FUSE HOLDER. THE EMPLOYEE WAS NOT WEARING A HARD HAT, RUBBER GLOVES, OR SLEVEES. THE EMPLOYEE RECONNECTED THE DEENERGIZED T AP TO THE FUSE HOLDER. WHEN HIS HEAD CONTACTED THE ENERGIZED TAP, HE WAS ELECTRO CUTED.
Victim
-
#1 Fatality Age 39 M
- Nature of injury
- 10
- Part of body
- 13
- Event type
- 6
- Source
- 15
- Occupation code
- 577
- Human factor
- 20
- Environmental factor
- 18
- Task assigned
- 1