Safety Incidents OSHA Severe Injury Reports · 2015–2025
105,991Records 71,450Employers 85,836Hospitalizations 27,959Amputations 2015-01-01 2025-11-30

OSHA Accident Investigation · Summary #722322

CENTRAL BLACKTOP CO. INC.

Event
E GI IV, ELECTRICAL, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, UNTRAINED
NAICS
000000
Inspection type
Accident-driven
Activity number
#101353803
Employer profile
CENTRAL BLACKTOP CO. INC.
Summary number
722322
Report ID
521700

Event description

ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

Investigation abstract

AN ASPHALT PLANT MANAGER WOULD OCCASIONALLY, DURING SLOW PERIODS AT THE PLANT, P OF THE SIX REMAINED ENERGIZED TO HOLD THE DAMPER OPEN. THIS CONDUCTOR WAS ENERGI ZED AT 120 VOLTS. CURRENT ENTRY AND EXIT WOUNDS WERE APPARENTLY FOUND ON THE EMP LOYEE'S HAND AND BACK. ERFORM MAINTENANCE ACTIVITIES. ON ONE OF THESE SLOW DAYS, HE WAS CHANGING AN AUT OMATIC DAMPER SERVO TO THE ASPHALT PROCESS EXHAUST SYSTEM. THE SYSTEM WAS SHUT D OWN AND THE CONTROLS WERE SET TO THE OFF POSITION. THE EMPLOYEE WAS LEANING BACK AGAINST A PIPE, STRIPPING SIX MOTOR CONDUCTORS TO THE SERVO WHEN HE WAS ELECTRO CUTED. INVESTIGATION REVEALED THAT THE EMPLOYEE WAS NOT AN ELECTRICIAN AND THAT THE COMPANY HAD NO LOCKOUT PROGRAM. THE BLUEPRINTS FOR THE CIRCUITRY WERE FOUND OPEN ON THE EMPLOYEE'S DESK. WITH THE CONTROLS IN THE OFF POSITION, FIVE OF THE SIX CONDUCTORS ON WHICH THE EMPLOYEE WAS WORKING WERE DEENERGIZED. HOWEVER, ONE

Victim

  1. #1 Fatality Age 34 M

    Nature of injury
    10
    Part of body
    3
    Event type
    12
    Source
    15
    Occupation code
    19
    Human factor
    1
    Environmental factor
    13
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.