105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #731034

OVERHEAD POWER LINE,ELECTRICAL,ELECTRICIAN,ELECTROCUTED,STREETLIGHTING,E PTD,ELEC UTILITY WORK,AERIAL LIFT

Event
OVERHEAD POWER LINE,ELECTRICAL,ELECTRICIAN,ELECTROCUTED,STREETLIGHTING,E PTD,ELEC UTILITY WORK,AERIAL LIFT
Linked inspection
No inspection record linked to this accident's victims.
Summary number
731034
Report ID
551800

Event description

ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU AERIAL LIFT

Investigation abstract

AN ELECTRICAL WORKER FOR A LIGHTING SERVICING COMPANY WAS PERFORMING MAINTENANCE LECTRIC SHOCK, AND HE DIED OF HIS INJURIES ABOUT 1 HOUR LATER IN A HOSPITAL. ON A STREETLIGHT THAT WAS LOCATED 35 FEET, 1 INCH ABOVE THE GROUND AND 8 FEET, 2 INCHES OUT FROM ITS SUPPORTING UTILITY POLE. THE EMPLOYEE WAS WORKING FROM AN UNGROUNDED AERIAL LIFT. HE RAISED THE AERIAL LIFT BUCKET TOWARD THE LIGHT. WHEN HE DID THIS, HE BROUGHT THE BUCKET INTO CONTACT WITH AN 8000-VOLT OVERHEAD POWER LINE THAT WAS LOCATED 30 FEET, 6 INCHES ABOVE THE GROUND AND 8 FEET, 6 INCHES F ROM THE POLE (IN THE SAME DIRECTION AS THE STREETLIGHT). THIS ENERGIZED THE BUCK ET, AND THE EMPLOYEE RECEIVED AN ELECTRIC SHOCK WHEN HE TOUCHED THE GROUNDED MET AL LIGHT WITH HIS RIGHT HAND. THE EMPLOYEE SUFFERED INTERNAL INJURIES FROM THE E

Victim

  1. #1 Fatality Age 26 M

    Nature of injury
    10
    Part of body
    31
    Event type
    13
    Source
    15
    Occupation code
    999
    Human factor
    6
    Environmental factor
    13
    Task assigned
    1