OSHA Accident Investigation · Summary #731158
VOLTAGE BACKFEED,ELEC PROTECT EQUIP,OVERHEAD POWER LINE,PROTECTIVE GROUNDING,ELECTRICAL,POWER LINE WORKER,ELECTROCUTED,LOCKOUT,E PTD,ELEC UTILITY WORK
Event description
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE
Investigation abstract
A power line worker was repairing a break in a 4000-volt overhead power line. He had deenergized two phases of the three-phase grounded-Y system, but did not te st or ground the line. The employee, who was not using electrical protective equ ipment, was electrocuted as he worked on the line. It was suspected that voltage backfeed on the third phase had energized the line.