105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #734962

ELECTRICAL,E GI VI,ELECTROCUTED,GROUND FAULT,INDUSTRIAL TRUCK,ELECTRIC CORD,ELEC EQUIPMENT--MISC

Event
ELECTRICAL,E GI VI,ELECTROCUTED,GROUND FAULT,INDUSTRIAL TRUCK,ELECTRIC CORD,ELEC EQUIPMENT--MISC
Linked inspection
No inspection record linked to this accident's victims.
Summary number
734962
Report ID
454510

Event description

ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC EQUIPMENT

Investigation abstract

AN INDUSTRIAL TRUCK (PORTER, INC., SERIAL NUMBER 695-785) POWERED BY A 25-HORSEP OWER MOTOR HAD BEEN MODIFIED TO OPERATE AS A FURNACE STOKER. THE FURNACE STOKER OPERATED AT 480 VOLTS. AN EMPLOYEE (AN ELECTRIC EQUIPMENT REPAIRER) HAD WIRED TH E POWER SUPPLY CORD TO THE FURNACE STOKER SO THAT THE GROUNDING CONDUCTOR WAS CO NNECTED TO ONE OF THE PHASE CONDUCTORS. THE WIRING ERROR HAD CAUSED FUSES TO OPE N AT LEAST TWICE BEFORE. HOWEVER, THIS TIME, UPON REENERGIZING THE CIRCUIT, THE GROUNDING CONDUCTOR SEPARATED AT A REMOTE PANELBOARD, LEAVING THE FRAME OF THE F URNACE STOKER ENERGIZED. THE ELECTRIC EQUIPMENT REPAIRER WAS ELECTROCUTED WHEN H E TOUCHED THE FURNACE STOKER.

Victim

  1. #1 Fatality Age 28 M

    Nature of injury
    10
    Part of body
    4
    Event type
    13
    Source
    15
    Occupation code
    533
    Human factor
    1
    Environmental factor
    11
    Task assigned
    1