105,313Records 71,083Employers 85,290Hospitalizations 27,770Amputations 2015-01-01 2025-10-31
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Accident Investigation · Summary #810101

ELECTRICAL,ELECTROCUTED,E C,GROUND FAULT,BONDING,ELECTRIC CONDUCTOR,SYSTEM GROUNDING,ELECTRIC GENERATOR

Event
ELECTRICAL,ELECTROCUTED,E C,GROUND FAULT,BONDING,ELECTRIC CONDUCTOR,SYSTEM GROUNDING,ELECTRIC GENERATOR
Linked inspection
No inspection record linked to this accident's victims.
Summary number
810101
Report ID
453710

Event description

ELECTRIC SHOCK - GROUND FAULT IN PORTABLE GENERATOR

Investigation abstract

AN EMPLOYEE WAS TOUCHING A THE METAL FRAME OF A PORTABLE GENERATOR. AN ABRADED C ONDUCTOR INSIDE A PANEL WAS FAULTED TO THE GENERATOR'S FRAME. THE GROUNDING ELEC TRODE AND BONDING CONDUCTOR WERE INEFFECTIVE, ALLOWING THE FRAME OF THE GENERATO R TO BECOME ENERGIZED AT A LOW VOLTAGE. THE EMPLOYEE, WHO WAS STANDING ON WET GR OUND, WAS ELECTROCUTED.

Victim

  1. #1 Fatality Age 21 M

    Nature of injury
    10
    Part of body
    29
    Event type
    12
    Source
    15
    Occupation code
    598
    Human factor
    6
    Environmental factor
    13
    Hazardous substance
    8870
    Task assigned
    1

Codes shown verbatim from OSHA's accident-investigation database. A human-readable decoder is coming in a future release once the accident_lookup2 dictionary is loaded.