SLATINGTON, PA —
OSHA Inspection: P P & L, INC.
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of P P & L, INC. in WASHINGTON TOWNSHIP, SLATINGTON, PA 18080 (NAICS 000000). OSHA activity number 100388370.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- P P & L, INC.
- Site address
- WASHINGTON TOWNSHIP
- City
- SLATINGTON
- State
- PA
- ZIP
- 18080
- Mailing
- 2 NORTH 9TH STREET, P.O. BOX 3500, ALLENTOWN, PA 18101
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 2
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Sep 23, 1988
- Abate by
- Sep 1, 1989
- Penalty
- Initial $640 · Current $350 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to electrocution and/or fall hazards: a) Construction - Line employees climb electrical transmission/ distribution line towers (Company #59733/551571) to perform visual inspection and/or repairs. An unguarded helper climbed the emergency side of the tower which was improperly grounded, was not marked to easily distinguish the energized side and the employee was inadequately trained in safety related work practices associated with the specific job assignment, May 14, 1988. Among other methods, feasible and acceptable abatement methods are: 1) The teaching of job skills (climbing) and work practices should be improved. The necessary job skills and work procedures should be identified and systematically taught. A formal accounting shouldbe maintained of skills acquired and procedures mastered to verify training and to certify employee qualifications. 2) When a de-energenized line and an energized line (66 KV or above) parallel each other within 100 feet and any work is possible on the de-energized line conductors (all phase wires and overhead static wires) the conductors should be short-circuited and grounded and the maximum distance between grounds is two (2) miles or less. 3) When climbing the energized side of a electrical transmission tower, employees should not place their body in any position from which a slip would tend to bring their body toward exposed parts which are at an electrical potential different from the employees body. 4) PP&L Safety Rule 18.12 (on double circuit lines in excess of 15 KV, with a circuit on each side of the pole, tower or structure, where on circuit is de-energized and grounded, warning flags shall be placed approximately 8 feet above the ground to indicate the energized circuit) should be enforced.
Recent events (2)
- — F (S) $350.00
- — Z (S) $640.00
More inspections at P P & L, INC.
View P P & L, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 100388370.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.