Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: P P & L, INC.

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of P P & L, INC. in WASHINGTON TOWNSHIP, SLATINGTON, PA 18080 (NAICS 000000). OSHA activity number 100388370.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch P P & L, INC. — free Get an email when a new federal OSHA severe-injury report for P P & L, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
P P & L, INC.
Site address
WASHINGTON TOWNSHIP
City
SLATINGTON
State
PA
ZIP
18080
Mailing
2 NORTH 9TH STREET, P.O. BOX 3500, ALLENTOWN, PA 18101
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
2
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 08 1 instance 1 exposed
Issued
Sep 23, 1988
Abate by
Sep 1, 1989
Penalty
Initial $640 · Current $350 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that employees were exposed to
electrocution and/or fall hazards:
a) Construction - Line employees climb electrical transmission/
distribution line towers (Company #59733/551571) to perform visual
inspection and/or repairs. An unguarded helper climbed the emergency
side of the tower which was improperly grounded, was not marked to
easily distinguish the energized side and the employee was
inadequately trained in safety related work practices associated
with the specific job assignment, May 14, 1988.
Among other methods, feasible and acceptable abatement methods are:
1) The teaching of job skills (climbing) and work practices should be
improved. The necessary job skills and work procedures should be
identified and systematically taught. A formal accounting shouldbe
maintained of skills acquired and procedures mastered to verify
training and to certify employee qualifications.
2) When a de-energenized line and an energized line (66 KV or above)
parallel each other within 100 feet and any work is possible on the
de-energized line conductors (all phase wires and overhead static
wires) the conductors should be short-circuited and grounded and the
maximum distance between grounds is two (2) miles or less.
3) When climbing the energized side of a electrical transmission tower,
employees should not place their body in any position from which a
slip would tend to bring their body toward exposed parts which are
at an electrical potential different from the employees body.
4) PP&L Safety Rule 18.12 (on double circuit lines in excess of 15 KV,
with a circuit on each side of the pole, tower or structure, where
on circuit is de-energized and grounded, warning flags shall be
placed approximately 8 feet above the ground to indicate the
energized circuit) should be enforced.
Recent events (2)
  • — F (S) $350.00
  • — Z (S) $640.00

View P P & L, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 100388370.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.