Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,473Inspections Most recent open 2026-07-28 Last loaded 2026-07-31

OSHA Inspection: W. R. MEADOWS OF PA, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of W. R. MEADOWS OF PA, INC. in 2100 MONROE ST., P.O. BOX 2284, YORK, PA 17405 (NAICS 000000). OSHA activity number 100414408.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch W. R. Meadows of PA, INC. — free Get an email when a new federal OSHA severe-injury report for W. R. Meadows of PA, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2100 MONROE ST., P.O. BOX 2284
City
YORK
State
PA
ZIP
17405
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
3999
Employees
23
Ownership type
A
Industry flags
Manufacturing safety.

5 citations on file for this inspection.

5(a)(1)

Serious 3 instances 1 exposed
Issued
Oct 16, 1986
Abate by
Oct 21, 1986
Penalty
Initial $480 · Current $480
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that employees were exposed to
burn hazards from hot asphalt in the event of tank rupture during
filling from inadequate and/or clogged venting:
a) Asphalt Storage Tank - 20,000 gallon above ground horizontal tank
had inadequate emergency venting and the three (3) inch vent was
clogged, May 2 and May 6, 1986.
Among other methods, one feasible and acceptable method to correct
the hazard is to install venting, meeting the requirements of UL 142,
Section 10.3 Steel above ground tanks for flammable and combustible
liquids and ensuring vents remain open.

1910.23 C01

Serious 1 instance 1 exposed
Issued
Oct 16, 1986
Abate by
Oct 21, 1986
Penalty
Initial $240 · Current $175 Reduced
Recent events (2)
  • — I (S) $175.00
  • — Z (S) $240.00

1910.252 A02 IIIB

Serious 1 instance 2 exposed
Issued
Oct 16, 1986
Abate by
Oct 21, 1986
Penalty
Initial $240 · Current $175 Reduced
Recent events (2)
  • — I (S) $175.00
  • — Z (S) $240.00

1910.252 A02 IVA

Serious 1 instance 2 exposed
Issued
Oct 16, 1986
Abate by
Oct 21, 1986

1910.252 A02 IVC

Serious 1 instance 2 exposed
Issued
Oct 16, 1986
Abate by
Oct 21, 1986

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 100414408.