GOLDEN, CO —
OSHA Inspection: COORS BREWING COMPANY, POWER UTILITY DIVISION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of COORS BREWING COMPANY, POWER UTILITY DIVISION in 12TH AND EAST STREETS, BC #110, GOLDEN, CO 80401 (NAICS 000000). OSHA activity number 100671452.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COORS BREWING COMPANY, POWER UTILITY DIVISION
- Site address
- 12TH AND EAST STREETS, BC #110
- City
- GOLDEN
- State
- CO
- ZIP
- 80401
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4961
- Employees
- 6700
- Ownership type
- A
Citations
12 citations on file for this inspection.
5(a)(1)
- Issued
- May 17, 1990
- Abate by
- Jun 4, 1990
- Penalty
- Initial $810 · Current $810
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about November 23, 1989 employees working in boiler 4 building basement were exposed to the hazard of flying metal and steam burns created by the blowout of an undersized relief valve which was located between turbine discharge exhaust and the first main stop valve on the exhaust discharge side of turbine No. 1. Among other methods, one feasible and acceptable abatement method to correct this hazard is to upgrade the size of the existing turbine exhaust outlet relief valve for the No. 1 feed water pump and to conform with standard recommended engineering requirements of the most recent A.S.M.E. boiler and pressure vessel code, section VIII; in accordance with requirements of paragraphs UG-125 through UG-134.
Recent events (2)
- — I (S) $810.00
- — Z (S) $810.00
5(a)(1)
- Issued
- May 17, 1990
- Abate by
- Jun 4, 1990
- Penalty
- Initial $810 · Current $810
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about November 23, 1989 employees working in boiler 4 building basement were exposed to the potential hazard of flying metal and steam burns due to the absence of a required relief valve located between turbine exhaust discharge and the first main stop valve on the exhaust discharge side of turbine No. 4. Among other methods, one feasible and acceptable abatement method to correct this hazard is to install a properly rated relief valve in the system between turbine exhaust discharge and the first main stop valve on the exhaust discharge side of turbine No. 4 and to conform with standard recommended engineering requirements.
Recent events (2)
- — I (S) $810.00
- — Z (S) $810.00
1910.23 C01
- Issued
- May 17, 1990
- Abate by
- Aug 4, 1990
- Penalty
- Initial $210 · Current $210
Recent events (2)
- — I (S) $210.00
- — Z (S) $210.00
1910.23 C02
- Issued
- May 17, 1990
- Abate by
- Aug 4, 1990
- Penalty
- Initial $300 · Current $300
Recent events (2)
- — I (S) $300.00
- — Z (S) $300.00
1910.68 B11 III
- Issued
- May 17, 1990
- Abate by
- Jun 4, 1990
- Penalty
- Initial $360 · Current $360
Recent events (2)
- — I (S) $360.00
- — Z (S) $360.00
1910.106 D04 I
- Issued
- May 17, 1990
- Abate by
- Aug 4, 1990
Recent events (2)
- — I (S)
- — Z (S)
1910.307 B
- Issued
- May 17, 1990
- Abate by
- Jun 10, 1990
- Penalty
- Initial $810 · Current $810
Recent events (2)
- — I (S) $810.00
- — Z (S) $810.00
1910.23 D01 II
- Issued
- May 17, 1990
- Abate by
- Jun 10, 1990
Recent events (2)
- — I (O)
- — Z (O)
1910.106 D04 IV
- Issued
- May 17, 1990
- Abate by
- Jan 1, 1991
Recent events (2)
- — I (O)
- — Z (O)
1910.305 G01 III
- Issued
- May 17, 1990
- Abate by
- Jun 10, 1990
5(a)(1)
- Issued
- May 17, 1990
- Abate by
- Jun 4, 1990
- Penalty
- Initial $810 · Current $810
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about November 23, 1989, employees working in boiler 4 building basement were exposed to the hazard of flying metal and steam burns created by the blowout of an undersized relief valve which was located between turbine discharge exhaust and the first main stop valve on the exhaust discharge side of turbine No. 1. Among other methods, one feasible and acceptable method to correct this hazard is to upgrade the size of the existing turbine exhaust outlet relief valve for the No. 1 feed water pump and to conform with standard recommended engineering requirements of most recent A.S.M.E. boiler and pressure vessel code, section VIII: in accordance with requirements of paragraphs UG-125 through UG-134.
Recent events (2)
- — I (S) $810.00
- — Z (S) $810.00
5(a)(1)
- Issued
- May 17, 1990
- Abate by
- Jun 4, 1990
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about November 23, 1989, employees working in boiler 4 building basement were exposed to potential hazard of flying metal and steam burns due to the absence of a required relief valve located between turbine exhaust discharge and the first main stop valve on the exhaust discharge side of turbine No. 4. Among other methods, one feasible and acceptable method to correct this hazard is to install a properly rated relief valve in the system between turbine exhaust discharge and the first main stop valve on the exhaust discharge side of turbine No. 4 and to conform with standard recommended engineering requirements of the most recent A.S.M.E.
Recent events (2)
- — I (S)
- — Z (S)
More inspections at Coors Brewing Company, Power Utility Division
View Coors Brewing Company, Power Utility Division's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 100671452.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.