ELIZABETH, NJ ·
OSHA Inspection: AUSIMONT, INC.
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of AUSIMONT, INC. in 8 NORTH AVE. EAST, ELIZABETH, NJ 07201 (NAICS 000000). OSHA activity number 100803824.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AUSIMONT, INC.
- Site address
- 8 NORTH AVE. EAST
- City
- ELIZABETH
- State
- NJ
- ZIP
- 07201
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2869
- Employees
- 100
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
6 citations on file for this inspection.
1910.37 K02
- Issued
- Mar 21, 1988
- Abate by
- Mar 24, 1988
- Penalty
- Initial $1,000 · Current $1,000
Recent events (2)
- · F (S) $1000.00
- · Z (S) $1000.00
1910.156 B01
- Issued
- Mar 21, 1988
- Abate by
- Apr 21, 1988
- Penalty
- Initial $1,000 · Current $600 Reduced
Recent events (2)
- · F (S) $600.00
- · Z (S) $1000.00
5(a)(1)
- Issued
- Mar 21, 1988
- Abate by
- Mar 24, 1988
- Penalty
- Initial $10,000 · Current $600 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: On or about 10/13/88 the employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of fire/explosion and the release of toxic gases/vapors which could result in serious bodily and fatal injuries. Hazardous toxic chemicals which were indentified to be imcompatible by their Material Safety Data Sheets and National Fire Protection Association Chapter 49-"Hazardous Chemical Data" were stored together: a-Polymer Building, 4th floor, North corner 1) Acetic Acid-Class III B Combustible-2.5 liter; 4 per box; 7 boxes Incompatible with strong oxidizers; strong caustics; Hydrogen Peroxide; Sodium Hydroxide; Potassium Persulfate and Sodium Metabisulfite. 2) Sodium Hydroxide-Caustic soda-16 boxes Incompatible with Flammable liquids; Alcohol; Trichoroethylene stored with Methanol. 3) Potassium Persulfate-Oxidizer-(7) 55 gallon drums Incompatible with acids; combustible material; oxidizable material stored with Hydrogen Peroxide. 4) Sodium Metabisulfite/Sodium Disulfite-1.1 liter, 4 bottles Incompatible with acids; oxidizing agents; metals-stored with Hydrogen Peroxide. 5) Chloroform-Depressant-2.0 liter, 20 bottles Incompatible with caustics; Sodium; Potassium; Sodium Hydroxide; Oxidizing Agents; Methanol stored with Sodium Hydroxide, and Hydrogen Peroxide. b-Outdoor Chemical Storage Cage, Southwest corner 1) Sulfuric Acid-Approximately 8 bottles Incompatible with alcohol: Oxidizing Agents-stored with Ethyl Acetate; Ammonium Hydroxide. One feasible and acceptable abatement method, among others, to correct this hazard is to separate the chemicals in storage according to type and compatibility to each other as prescribed in the Material Safety Data Sheets and National Fire Protection Accosiation, Chapter #49.
Recent events (2)
- · F (W) $600.00
- · Z (W) $10000.00
5(a)(1)
- Issued
- Mar 21, 1988
- Abate by
- Apr 5, 1988
- Penalty
- Initial $10,000 · Current $600 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970 and/or 29 CFR 1910.106(h)(8)(i): On or about 10/13/87 the employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazard of explosion/fire and inhalation of toxic vapors which could result in serious/fatal bodily inuries: a) On 10/13/87 a chemical explosion occurred at the Halar Polymer Building Recovery System, rupturing the U-2 vessel and associated equipment due to equipment fire. A feasible and acceptable abatement method among others, to correct this hazard is to institute a Preventative Maintenance Program that would provide for the periodic inspection of equipment, i.e., Flanges, Pipes, Valves, Gauges, Pressure Relief Valves, Pumps and Vessels, to detect deterioration trends that would cause equipment to fail. In addition the exclusion of air from the Halar Recovery System which is critical since air can violent disproportionation of the Chlorotrifluoroethylene (CTFE).
Recent events (2)
- · F (W) $600.00
- · Z (W) $10000.00
1910.307 B03
- Issued
- Mar 21, 1988
- Abate by
- Mar 24, 1988
- Penalty
- Initial $120,000 · Current $72,000 Reduced
Recent events (2)
- · F (W) $72000.00
- · Z (W) $120000.00
1904.2 A
- Issued
- Mar 21, 1988
- Abate by
- Apr 4, 1988
Recent events (2)
- · F (O)
- · Z (O)
More inspections at Ausimont, INC.
View Ausimont, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 100803824.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.