OSHA Inspection: PUBLIC SERVICE OF N.H.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PUBLIC SERVICE OF N.H. in CHESTNUT ST., DOVER, NH 03820 (NAICS 000000). OSHA activity number 100851997.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Public Service of N.H. for free Get an email when a new federal OSHA severe-injury report for Public Service of N.H. is published. One employer, no account, unsubscribe in one click.
Site address
CHESTNUT ST.
City
DOVER
State
NH
ZIP
03820
Mailing
74 OLD DOVER RD., ROCHESTER, NH 03105
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
5
Ownership type
A
Industry flags
Manufacturing safety.

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 08 1 instance 5 exposed
Issued
Aug 16, 1990
Abate by
Sep 4, 1990
Penalty
Initial $560 · Current $560
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that employees were exposed to
hazards of shocks and electrocution:
a) On or about March 15, 1990, and at times prior thereto at Switch
Cabinet number 3, located on the east side of Chestnut Street and
on the north side of the Coheco River in Dover, NH, foremen, linemen,
and electricians were exposed to shocks and possible electrocution
while troubleshooting underground distribution cabes in that the
employees with no protective equipment were permitted to approach
electrical conductors which were live or where the condition of the
conductors was not known.
ABATEMENT: A feasible and acceptable abatement method, among others, to
correct this hazard is to permit only the minimum number of qualified
persons, and preferably one person, with appropriate protective
equipment, to approach the hazardous area and all others maintain the
minimum established distances for the voltage being worked.