MARION, IL ·
OSHA Inspection: VETERANS ADMINISTRATION MEDICAL CENTER OF MARION
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of VETERANS ADMINISTRATION MEDICAL CENTER OF MARION in 2401 WEST MAIN STREET, MARION, IL 62959 (NAICS 000000). OSHA activity number 102577814.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VETERANS ADMINISTRATION MEDICAL CENTER OF MARION
- Site address
- 2401 WEST MAIN STREET
- City
- MARION
- State
- IL
- ZIP
- 62959
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 8062
- Employees
- 500
- Ownership type
- Federal government (D)
Citations
1 citation on file for this inspection.
10201 A
- Issued
- Sep 29, 1988
- Abate by
- Dec 31, 1988
General-duty citation text
Section 1-201(a) of Executive Order 12196 of February 26, 1980: The head of the agency did not furnish to employees places and conditions of employment that were free from recognized hazards that were causing or likely to cause death or serious physical harm in that: Inadequate preventive maintenance and repair practices, procedures and/ or conditions increased the likelihood of fires and/or explosions in in combination natural gas/fuel oil, dry back, fire-tube boilers. The established preventive maintenance and repair procedures at the Veterans Administration Medical Center (VAMC) located in Marion, IL were not properly implemented, communicated or enforced. Among other methods, one feasible and acceptable method to abate this hazard is to establish a formalized preventive maintenance and repair program specific to the types of boilers operated at the Marion, IL facility. This procedure shall be based on recommendations contained in VA manual CP-34, Part 1, DM&S Supplement, MP-3. Essential elements of this program shall include, but not necessarily limited to the following: 1) Modify the boiler operators's "Standard Operating Procedures" to incorporate preventive maintenance procedures specific to the boilers operated at the Marion, IL facility. These procedures shall describe the type and frequency of preventive maintenance to be performed plus the proper methods by which it is to be done. Specific instructions for employee safety while performing this work shall also be incorporated when appropriate. 2) Establish a means of logging boiler repair work to supplement established facility work order procedures so that the progress of this repair work which may extend over a period of time, can easily be monitored by the boiler supervisor and his superiors. The logging method shall provide a comprehensive record of the entire repair operation from the point at which need for repair was discovered until it is completed, including notations explaining significant delays; reasons for not performing the recommended repair and additional safeguards that will be taken to assure the boilers are operated in a safe manner if a decision is made to run them with broken defective or substandard equipment. 3) Provide training to the boiler operators and the supervisor in the requirements of the preventive maintenance and repair program outlined above along with specific procedures for performing the required preventive maintenance. In addition, the hazards associated with failure to perform these functions and performing them improperly shall be discussed. 4) Monitor the preventive maintenance and repair program at both the employee and supervisory level to ensure that the required preventive maintenance is being performed and that defective equipment discovered either during inspection or operation of the boilers is promptly repaired. Consideration shall be given to the use of logs or checklists to be completed by the operators and reviewed, at designated intervals, by the boiler supervisor and his superiors to assure the above functions are actually being carried out. 5) Administer appropriate disciplinary measures, consistent with other VA policies on this subject, for any employee who fails to follow the requirements set forth in the preventive maintenance and repair program. 6) Review and evaluate standard operating procedures, logs, checklists, training and enforcement measures on a periodic basis to ensure their continued adequacy and effectiveness. Any changes made to the above shall be thoroughly discussed with the supervisor and boiler operators, allowing opportunity for their input, prior to implementing them. The rationale behind why needed changes are being made shall also be discussed.