Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LITE TECH, INC.

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of LITE TECH, INC. in 1718 PEACHTREE STREET, N.W., ATLANTA, GA 30309 (NAICS 000000). OSHA activity number 102829157.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Lite Tech, INC. — free Get an email when a new federal OSHA severe-injury report for Lite Tech, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
LITE TECH, INC.
Site address
1718 PEACHTREE STREET, N.W.
City
ATLANTA
State
GA
ZIP
30309
Mailing
332 NAVARRE DRIVE, STONE MOUNTAIN, GA 30087
Inspection type
Accident-driven (A)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
1731
Employees
2
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance
Issued
Dec 28, 1989
Abate by
Jan 2, 1990
Penalty
Initial $1,000 · Current $500 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that the employer failes to
ensure that all electrical faults were cleared from systems that have
been de-energized by a circuit protective device prior to manually re-
energizing circuit in accordance with NFPA 70E, Part II, Chapter 3.
a) Peachtree 25th building - 6th floor south tower - Electrical Closet -
A fault created in the system was not cleared prior to a 200 amp fuse
being removed and a new fuse being re-installed.
A feasible and acceptable method of abatement includes but is not
limited to ensuring that all electrical faults are fully cleared from
the system prior to attempting to re-energize the system.
Recent events (2)
  • — I (S) $500.00
  • — Z (S) $1000.00

5(a)(1)

Serious Gravity 10 1 instance
Issued
Dec 28, 1989
Abate by
Jan 2, 1990
Penalty
Initial $1,000 · Current $500 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that the employer failed to
ensure the use of the fuse handling equipment, suitably insulated for
circuit voltage when terminals are energized, in accordance with NFPA
70E, Part II, Chapter 1.
a) Peachtree 25th Building - 6th floor South Tower - Electrical Closet -
Fuse handling equipment, suitably insulated for circuit voltage, was
not used to removed or install fuses if the fuse terminals are
energized.
Feasible and acceptable method of abatement includes but is not limited
to ensuring the use of fuse handling equipment, suitably insulated
insulated for circuit voltage, or fully de-energizing the electrical
system prior to removing or installing fuses.