ATLANTA, GA —
OSHA Inspection: LITE TECH, INC.
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of LITE TECH, INC. in 1718 PEACHTREE STREET, N.W., ATLANTA, GA 30309 (NAICS 000000). OSHA activity number 102829157.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LITE TECH, INC.
- Site address
- 1718 PEACHTREE STREET, N.W.
- City
- ATLANTA
- State
- GA
- ZIP
- 30309
- Mailing
- 332 NAVARRE DRIVE, STONE MOUNTAIN, GA 30087
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 1731
- Employees
- 2
- Ownership type
- A
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Dec 28, 1989
- Abate by
- Jan 2, 1990
- Penalty
- Initial $1,000 · Current $500 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that the employer failes to ensure that all electrical faults were cleared from systems that have been de-energized by a circuit protective device prior to manually re- energizing circuit in accordance with NFPA 70E, Part II, Chapter 3. a) Peachtree 25th building - 6th floor south tower - Electrical Closet - A fault created in the system was not cleared prior to a 200 amp fuse being removed and a new fuse being re-installed. A feasible and acceptable method of abatement includes but is not limited to ensuring that all electrical faults are fully cleared from the system prior to attempting to re-energize the system.
Recent events (2)
- — I (S) $500.00
- — Z (S) $1000.00
5(a)(1)
- Issued
- Dec 28, 1989
- Abate by
- Jan 2, 1990
- Penalty
- Initial $1,000 · Current $500 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that the employer failed to ensure the use of the fuse handling equipment, suitably insulated for circuit voltage when terminals are energized, in accordance with NFPA 70E, Part II, Chapter 1. a) Peachtree 25th Building - 6th floor South Tower - Electrical Closet - Fuse handling equipment, suitably insulated for circuit voltage, was not used to removed or install fuses if the fuse terminals are energized. Feasible and acceptable method of abatement includes but is not limited to ensuring the use of fuse handling equipment, suitably insulated insulated for circuit voltage, or fully de-energizing the electrical system prior to removing or installing fuses.
Recent events (2)
- — I (S) $500.00
- — Z (S) $1000.00
More inspections at Lite Tech, INC.
View Lite Tech, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in GA
Source