CLEVELAND, OH —
OSHA Inspection: COYNE TEXTILE SERVICES
Accident-driven inspection · Health discipline
At a glance
On , OSHA opened an accident-driven health inspection of COYNE TEXTILE SERVICES in 12315 KIRBY AVENUE, CLEVELAND, OH 44108 (NAICS 000000). OSHA activity number 103015251.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COYNE TEXTILE SERVICES
- Site address
- 12315 KIRBY AVENUE
- City
- CLEVELAND
- State
- OH
- ZIP
- 44108
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 7218
- Employees
- 120
- Ownership type
- A
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Mar 17, 1997
- Abate by
- Jul 1, 1997
- Penalty
- Initial $2,975 · Current $2,082 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employmnent and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: Shop towels which were damp with flammable and combustible liquids were not handled or processed in a manner that would serve to prevent fires and explosion. Note: Measures to prevent ignition include, but are not limited to, the following: 1. Installation of an exhaust system to prevent the accumulation of flammable vapors in the washing machine and in the trenches below and behind the machine. 2. Replacement of all electrical equipment in the area with equipment designed for class 1 division 1 and class 1 division 2 as required. See citation 1 item 1b and 1c for specific guidance.
Recent events (2)
- — I (S) $2082.00
- — Z (S) $2975.00
5(a)(1)
- Issued
- Mar 17, 1997
- Abate by
- Jul 1, 1997
General-duty citation text
29 CFR 1910.106(e)(7)(i)(b): Electrical equipment in locations where flammable vapor-air mixtures may exist under normal operations were not approved for Class 1 division 1 locations. The area shall extend 5 feet in all directions from all points of vapor liberation, and the entire pit area if any part of the pit is located in the class 1, division 1 area: Electrical equipment in the area was not approved for class 1 division 1 areas: Equipment in the area includes but is not limited to the following: a) Interlock switch located on top of machine was directly in a point of vapor liberation at the top of the wash machine. b) Electric motor at the south end of the machine was directly in a point of vapor liberation at the top of the wash machine. c) An electrical box, containing a switch for a fan was located on the wall behind the machine, 39 inches from a point of vapor liberation at the top of the wash machine. d) The electrical box, and wiring from the box located on the south end of the machine was located 12" from a point of vapor liberation on the front of the machine and 15 inches from the front trench which becomes a point of vapor liberation when the water is dumped from the machine. Note: In lieu of providing class 1 division 1 electrical equipment at all locations, a ventilation system installed on the wash machine and on the water trenches below the machines, which is effective in maintaining levels of contaminant below 25 percent of the LEL may be utilized. This system should be maintained in good repair and means to verify it's effectiveness should be installed.
5(a)(1)
- Issued
- Mar 17, 1997
- Abate by
- Jul 1, 1997
General-duty citation text
29 CFR 1910.106(e)(7)(i)(c): Electrical equipment which was installed in locations where flammable vapor-air mixtures may exist under abnormal conditions and for a distance beyond Class 1 division 1 areas was not of a design that was approved for Class 1 division 2 locations. These locations include an area 20 feet horizontally and 3 feet vertically beyond Class 1 division 1 locations: Electrical equipment in the area was not approved for class 1 division 1, areas: Equipment in the area include, but is not limited to the following: a) Interlock switch located on top of machine was directly in a point of vapor liberation at the top of the wash machine. b) Electric motor at the south end of the machine was directly in a point of vapor liberation at the top of the wash machine. c) An electrical box, containing a switch for a fan was located on the wall behind the machine is 39 inches from a point of vapor liberation at the top of the wash machine. d) The electrical box, and wiring from the box located on the south end of the machine was located 12" from a point of vapor liberation on the front of the machine and 15 inches from the front trench which becomes a point of vapor liberation when the water is dumped from the machine. Note: In lieu of providing class 1 division 1 electrical equipment at all locations, a ventilation system installed on the wash machine and on the water trenches below the machines, which is effective in maintaining levels of contaminant below 25 percent of the LEL may be utilized. This system should be maintained in good repair and means to verify it's effectiveness should be installed.
More inspections at Coyne Textile Services
View Coyne Textile Services's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 103015251.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.