OSHA Inspection: COYNE TEXTILE SERVICES

Accident-driven inspection · Health discipline

On , OSHA opened an accident-driven health inspection of COYNE TEXTILE SERVICES in 12315 KIRBY AVENUE, CLEVELAND, OH 44108 (NAICS 000000). OSHA activity number 103015251.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Coyne Textile Services — free Get an email when a new federal OSHA severe-injury report for Coyne Textile Services is published. One employer, no account, unsubscribe in one click.
Site address
12315 KIRBY AVENUE
City
CLEVELAND
State
OH
ZIP
44108
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
7218
Employees
120
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 05 1 instance 4 exposed
Issued
Mar 17, 1997
Abate by
Jul 1, 1997
Penalty
Initial $2,975 · Current $2,082 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:
The employer did not furnish employmnent and a place of employment
which were free from recognized hazards that were causing or likely
to cause death or serious physical harm to employees in that
employees were exposed to:
Shop towels which were damp with flammable and combustible liquids
were not handled or processed in a manner that would serve to
prevent fires and explosion.
Note:
Measures to prevent ignition include, but are not limited to, the
following:
1.  Installation of an exhaust system to prevent the accumulation
of flammable vapors in the washing machine and in the trenches
below and behind the machine.
2.  Replacement of all electrical equipment in the area with
equipment designed for class 1 division 1 and class 1 division 2 as
required.  See citation 1 item 1b and 1c for specific guidance.
Recent events (2)
  • — I (S) $2082.00
  • — Z (S) $2975.00

5(a)(1)

Serious Gravity 05 4 instances 4 exposed
Issued
Mar 17, 1997
Abate by
Jul 1, 1997
29 CFR 1910.106(e)(7)(i)(b): Electrical equipment in locations
where flammable vapor-air mixtures may exist under normal
operations were not approved for Class 1 division 1 locations.  The
area shall extend 5 feet in all directions from all points of vapor
liberation, and the entire pit area if any part of the pit is
located in the class 1, division 1 area:
Electrical equipment in the area was not approved for class 1
division 1 areas:
Equipment in the area includes but is not limited to the following:
a) Interlock switch located on top of machine was directly in a
point of vapor liberation at the top of the wash machine.
b) Electric motor at the south end of the machine was directly in
a point of vapor liberation at the top of the wash machine.
c) An electrical box, containing a switch for a fan was located on
the wall behind the machine, 39 inches from a point of vapor
liberation at the top of the wash machine.
d) The electrical box, and wiring from the box located on the south
end of the machine was located 12" from a point of vapor liberation
on the front of the machine and 15 inches from the front trench
which becomes a point of vapor liberation when the water is dumped
from the machine.
Note:
In lieu of providing class 1 division 1 electrical equipment at all
locations, a ventilation system installed on the wash machine and
on the water trenches below the machines, which is effective in
maintaining levels of contaminant below 25 percent of the LEL may
be utilized.  This system should be maintained in good repair and
means to verify it's effectiveness should be installed.

5(a)(1)

Serious Gravity 05 2 instances 8 exposed
Issued
Mar 17, 1997
Abate by
Jul 1, 1997
29 CFR 1910.106(e)(7)(i)(c): Electrical equipment which was
installed in locations where flammable vapor-air mixtures may exist
under abnormal conditions and for a distance beyond Class 1
division 1 areas was not of a design that was approved for Class 1
division 2 locations.  These locations include an area 20 feet
horizontally and 3 feet vertically beyond Class 1 division 1
locations:
Electrical equipment in the area was not approved for class 1
division 1, areas:
Equipment in the area include, but is not limited to the following:
a) Interlock switch located on top of machine was directly in a
point of vapor liberation at the top of the wash machine.
b) Electric motor at the south end of the machine was directly in
a point of vapor liberation at the top of the wash machine.
c) An electrical box, containing a switch for a fan was located on
the wall behind the machine is 39 inches from a point of vapor
liberation at the top of the wash machine.
d) The electrical box, and wiring from the box located on the south
end of the machine was located 12" from a point of vapor liberation
on the front of the machine and 15 inches from the front trench
which becomes a point of vapor liberation when the water is dumped
from the machine.
Note:
In lieu of providing class 1 division 1 electrical equipment at all
locations, a ventilation system installed on the wash machine and
on the water trenches below the machines, which is effective in
maintaining levels of contaminant below 25 percent of the LEL may
be utilized.  This system should be maintained in good repair and
means to verify it's effectiveness should be installed.