GOSHEN, OH ·
OSHA Inspection: SUBURBAN PROPANE L.P.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of SUBURBAN PROPANE L.P. in OHIO 28 & COZADDALE ROAD, GOSHEN, OH 45122 (NAICS 000000). OSHA activity number 103272159.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SUBURBAN PROPANE L.P.
- Site address
- OHIO 28 & COZADDALE ROAD
- City
- GOSHEN
- State
- OH
- ZIP
- 45122
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 5984
- Employees
- 19
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 25, 1996
- Abate by
- Nov 1, 1996
- Penalty
- Initial $4,500 · Current $1,900 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the hazards of fire and explosion from the ignition of flammable gas escaping from tanks being serviced or filled with liquid propane(LP): Ventilation in the Fill Room at the facility on May 28, 1996, was not adequate to prevent the accumulation of flammable LP gas in all parts of the Fill Room where it may be released or settle. Among other methods to correct this condition, the employer could: 1) Redesign and install an effective mechanical ventilation system which will provide an adequate purge of stagnate hydrocarbons in all parts of the room at no less than a minimum of 1 CFM (cubic foot per minute) of air flow per square foot of floor area of the Fill Room so that the entire floor area is vented in accordance with an industry consensus standard, NFPA (National Fire Protection Association) #58, or, 2) Provide natural ventilation openings in the Fill Room designed in accordance with current engineering design principles, to ensure the minimum 1 CFM per square foot of floor area rate and a uniform venting of the entire floor area as much as practical and in accordance with NFPA #58.
Recent events (2)
- · I (S) $1900.00
- · Z (S) $4500.00
1910.106 E02 IVA
- Issued
- Jun 14, 1996
- Abate by
- Jun 20, 1996
- Penalty
- Initial $1,500 · Current $1,200 Reduced
Recent events (2)
- · I (S) $1200.00
- · Z (S) $1500.00
1910.110 B17 II
- Issued
- Jun 14, 1996
- Abate by
- Jun 20, 1996
- Penalty
- Initial $1,875 · Current $1,200 Reduced
Recent events (2)
- · I (S) $1200.00
- · Z (S) $1875.00
1910.1200 F05 I
- Issued
- Jun 14, 1996
- Abate by
- Jun 20, 1996
- Penalty
- Initial $1,500 · Current $1,200 Reduced
Recent events (2)
- · I (S) $1200.00
- · Z (S) $1500.00
1910.1200 F05 II
- Issued
- Jun 14, 1996
- Abate by
- Jun 20, 1996
Recent events (2)
- · I (S)
- · Z (S)
1910.1200 G01
- Issued
- Jun 14, 1996
- Abate by
- Jun 20, 1996
- Penalty
- Initial $1,500
Recent events (2)
- · I (O)
- · Z (S) $1500.00
More inspections at Suburban Propane L.P.
View Suburban Propane L.P.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 103272159.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.