OSHA Inspection: PIG IMPROVEMENT COMPANY (PIC)

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PIG IMPROVEMENT COMPANY (PIC) in S11554 DYKE ROAD, SPRING GREEN, WI 53588 (NAICS 000000). OSHA activity number 106051931.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch PIG Improvement Company (PIC) for free Get an email when a new federal OSHA severe-injury report for PIG Improvement Company (PIC) is published. One employer, no account, unsubscribe in one click.
Site address
S11554 DYKE ROAD
City
SPRING GREEN
State
WI
ZIP
53588
Mailing
E4614 HWY 14/60, SPRING GREEN, WI 53588
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
0291
Employees
50
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 03 1 instance 4 exposed
Issued
Jan 17, 1997
Abate by
Jan 22, 1997
Penalty
Initial $1,125 · Current $1,125
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:  The hazard of exposure to electrical shock or
electrocution from wiring
which does not meet the requirements of the National Electrical Code
(NEC). In that:
1. Attachment plugs and connectors for the heat lamps in the farrowing
area were of not
dead-front construction.(NEC 410-56 f!)
2. Exposed noncurrent-carrying metal parts of fixed equipment (wall
mounted gas heaters
in the passageway between the farrowing units) were not grounded. (NEC
250-42,-43)
3. Flexible cords were being used to connect a space heater to a ceiling
outlet (as a
substitute for fixed wiring) in the gilthouse area. (NEC 400-8)
AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE ABATEMENT
METHOD TO CORRECT THIS HAZARD IS ....
1. Inspect all heating lamps to ensure they meet the requirements of the
National Electrical Code
that all 15 and 20 ampere attachment plugs and connections be dead-end
front construction.
2. Exposed noncurrent-carrying metal parts of fixed equipment should be
tested to make sure
they are properly grounded.
3. Install permanent wiring for the heater.