JAMAICA, NY ·
OSHA Inspection: CONSOLIDATED EDISON COMPANY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CONSOLIDATED EDISON COMPANY in MH 8816 N/S HILLSIDE AVE BET 202ND & 204TH ST., JAMAICA, NY 11430 (NAICS 000000). OSHA activity number 106824717.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONSOLIDATED EDISON COMPANY
- Site address
- MH 8816 N/S HILLSIDE AVE BET 202ND & 204TH ST.
- City
- JAMAICA
- State
- NY
- ZIP
- 11430
- Mailing
- 118-29 QUEENS BLVD., KEW GARDENS, NY 11375
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 3
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Nov 7, 1988
- Abate by
- Nov 7, 1988
- Penalty
- Initial $720 · Current $720
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: On May 11, 1988 employees were exposed to a "D" Fault-Fire, possible explosion from 27,000 volts minimum of 17,500 amps on an energized feeder cable. The feeder cable 5Q31 Located in manhole #8816 at Hillside Avenue & 202nd St., was not immediately removed from service and repaired as required in Con Edison E01184-3 (1/29/88) Distribution Underground Cable Joint Inspections "C" & "D" Faults. Employees were engaged in blanketing the swollen joint in order to work on another feeder cable. Feeders were submerged in water. Among other methods, one feasible and acceptable abatement method to correct this hazard is: Remove "D" Fault from line, do not enter manhole without de- energizing the feeder cable.
Recent events (2)
- · D (S) $720.00
- · Z (S) $720.00
More inspections at Consolidated Edison Company
View Consolidated Edison Company's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 106824717.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.