Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: CONSOLIDATED EDISON COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of CONSOLIDATED EDISON COMPANY in MH 8816 N/S HILLSIDE AVE BET 202ND & 204TH ST., JAMAICA, NY 11430 (NAICS 000000). OSHA activity number 106824717.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Consolidated Edison Company for free Get an email when a new federal OSHA severe-injury report for Consolidated Edison Company is published. One employer, no account, unsubscribe in one click.
Site address
MH 8816 N/S HILLSIDE AVE BET 202ND & 204TH ST.
City
JAMAICA
State
NY
ZIP
11430
Mailing
118-29 QUEENS BLVD., KEW GARDENS, NY 11375
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
3
Ownership type
Private (A)
Industry flags
Manufacturing safety.

1 citation on file for this inspection.

5(a)(1)

Deleted Serious Gravity 08 1 instance 2 exposed
Issued
Nov 7, 1988
Abate by
Nov 7, 1988
Penalty
Initial $720 · Current $720
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that employees were exposed to:
On May 11, 1988 employees were exposed to a "D" Fault-Fire, possible
explosion from 27,000 volts minimum of 17,500 amps on an energized
feeder cable.  The feeder cable 5Q31 Located in manhole #8816 at
Hillside Avenue & 202nd St., was not immediately removed from service
and repaired as required in Con Edison E01184-3 (1/29/88) Distribution
Underground Cable Joint Inspections "C" & "D" Faults.
Employees were engaged in blanketing the swollen joint in order to work
on another feeder cable.  Feeders were submerged in water.
Among other methods, one feasible and acceptable abatement method
to correct this hazard is:
Remove "D" Fault from line, do not enter manhole without de-
energizing the feeder cable.
Recent events (2)
  • · D (S) $720.00
  • · Z (S) $720.00

View Consolidated Edison Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 106824717.