BRONX, NY ·
OSHA Inspection: CON EDISON OF NEW YORK, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CON EDISON OF NEW YORK, INC. in S/E CORNER OF ALEXANDER AVE. & BRUCKNER BLVD., BRONX, NY 10461 (NAICS 000000). OSHA activity number 106828411.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CON EDISON OF NEW YORK, INC.
- Site address
- S/E CORNER OF ALEXANDER AVE. & BRUCKNER BLVD.
- City
- BRONX
- State
- NY
- ZIP
- 10461
- Mailing
- 310 E. KINGSBRIDGE RD., BRONX, NY 10461
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 1
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Feb 9, 1989
- Abate by
- Feb 12, 1989
- Penalty
- Initial $800 · Current $800
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: On 8-12-88 Location: Bruckner Blvd. and Alexander Ave. a) Employees were exposed to a type 11 "D" fault line, possible explosion from 13,000 volts on an energized feeder cable. The feeder cable 3M41 located in Manhole #509 was not immediately removed from service and repaired as required in Con Edison EO-1184-3 (1/29/88). Operation and Maintenance of Cable Procedures, Distribution and Underground Cable Joint Inspections "C" and "D" Faults. Employee was engaged in blanketing the swollen joint in for other employees to work in manhole. Among other methods, one feasible and acceptable abatement method to correct this hazard is: Remove "D" Fault from service, do not enter manhole without Denergizing the feeder cable.
Recent events (2)
- · J (S) $800.00
- · Z (S) $800.00
More inspections at CON Edison of NEW York, INC.
View CON Edison of NEW York, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 106828411.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.