Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: NORQUEST SEAFOODS INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NORQUEST SEAFOODS INC in M/V PRIBILOF-NAKNEK, NAKNEK, AK 99366 (NAICS 000000). OSHA activity number 107106353.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Norquest Seafoods INC — free Get an email when a new federal OSHA severe-injury report for Norquest Seafoods INC is published. One employer, no account, unsubscribe in one click.
Site address
M/V PRIBILOF-NAKNEK
City
NAKNEK
State
AK
ZIP
99366
Mailing
5245 SHILSHOLE AVE NW, SEATTLE, WA 98107
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
000000
SIC code (legacy)
2092
Employees
96
Ownership type
A
Industry flags
Maritime safety.

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 8 instances 96 exposed
Issued
Aug 11, 1997
Abate by
Aug 17, 1997
Penalty
Initial $5,000 · Current $2,500 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to a recognized hazard of electrical shock or burn:
(a)M/V Pribilof:  In the engine room, employees had occasion to work near
four
electrical outlet with reverse polarity when tested with Woodhead
electrical tester.
Among other methods, one feasible and acceptable abatement method to
correct
this hazard would be to remove and properly rewire the receptacles.
(b)M/V Pribilof:  In the engine room, a flexicord was used for electrical
wiring for
fluorescent lights.  This condition exposed employees to possible
electrical shock
or burn in the event of accidental contact with bare electrical conductors.
Among other methods, one feasible and acceptable abatement to correct this
hazard would be to remove the temporary wiring and install permanent
wiring to
the lights.
(c)M/V Pribilof:  In the engine room, the access stairway light was burned
out,
exposing employees to multiple injuries from tripping/slipping hazard.
Among other methods, one feasible and economical abatement method to
correct
this hazard would be to replace the burned out light bulbs.
(d)M/V Pribilof:  In the machine shop, there were four fluorescent lights
under 7
feet without proper covers or guards.  This condition exposed employees to
possible electric shock or burn in the event the light tubes were
accidentally
broken.
Among other methods, one feasible and acceptable abatement method to
correct
this hazard would be to install guards over the light tubes.
(e)M/V Pribilof:  In the refer room, the junction box cover was missing,
exposing
live wires to employees and the hazard to electrocution.
Among other methods, one feasible and economical method to correct this
hazard
to install a junction cover.
(f)M/V Pribilof:  In the Machine shop a 3" x 6" control junction box has a
missing
cover exposing employees to the hazard of electrical shock.
Among other methods, one feasible and acceptable method to abate the
hazard is
to install a control junction cover.
(g)M/V Pribilof:  In the weather deck behind the crane control box, is a
weatherproof receptacle without cover.  This condition exposed employees to
possible electrical shock or burn in the event the outlet is utilized and
energized
for other operations on deck.
Among other methods, one feasible and economical method is to install a
weatherproof receptacle cover.
(h)M/V Pribilof:  In the Generator room, employees had occasion to work
near an
electrical outlet with reverse polarity when tested with Woodhead
electrical tester,
exposing employees to hazards of electrical shock or burn.
Among other methods, one feasible and acceptable method to correct this
hazard
is to remove and properly rewire receptacles.
Recent events (2)
  • — I (S) $2500.00
  • — Z (S) $5000.00

1910.23 A08

Serious Gravity 10 1 instance 5 exposed
Issued
Aug 11, 1997
Abate by
Aug 14, 1997
Penalty
Initial $5,000 · Current $2,500 Reduced
Recent events (2)
  • — I (S) $2500.00
  • — Z (S) $5000.00

1910.106 E09 III

Serious Gravity 10 1 instance 5 exposed
Issued
Aug 11, 1997
Abate by
Aug 16, 1997
Penalty
Initial $5,000 · Current $2,500 Reduced
Recent events (2)
  • — I (S) $2500.00
  • — Z (S) $5000.00

1910.157 E02

Serious Gravity 05 1 instance 96 exposed
Issued
Aug 11, 1997
Abate by
Aug 17, 1997
Penalty
Initial $2,975 · Current $1,488 Reduced
Recent events (2)
  • — I (S) $1487.50
  • — Z (S) $2975.00

1910.179 B05

Deleted Serious Gravity 10 1 instance 96 exposed
Issued
Aug 11, 1997
Abate by
Aug 17, 1997
Penalty
Initial $5,000 · Current $5,000
Recent events (2)
  • — I (S) $5000.00
  • — Z (S) $5000.00

View Norquest Seafoods INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 107106353.