NIKISKI, AK ·
OSHA Inspection: NIPPON STEEL U.S.A.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NIPPON STEEL U.S.A. in STEELHEAD PLATFORM, BARGE KUROSHIO, NIKISKI, AK 99635 (NAICS 000000). OSHA activity number 107294936.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NIPPON STEEL U.S.A.
- Site address
- STEELHEAD PLATFORM, BARGE KUROSHIO
- City
- NIKISKI
- State
- AK
- ZIP
- 99635
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4491
- Employees
- 100
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
5(a)(1)
- Issued
- Oct 6, 1989
- Abate by
- Oct 18, 1989
- Penalty
- Initial $420 · Current $420
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to a recognized hazard of coming into contact with current carrying parts: a) Barge Kuroshio: Employees in the bow machine room had occasion to work near the 100 and 440 volt a.c. electrical switch gear panels that had open and exposed electrical current conductors. Lack of covers or other approved enclosures exposed the employees to the hazard of contacting energized parts, which could result in electrical shock, thermo burns or electrocution. Among other methods, one feasible and acceptable abatement method to correct this hazard is to install metal cover plates over the back of each electrical panel or install a gate and lock at the access points to the electrical panels, and secure such that access is only allowed to qualified personnel.
1910.219 D01
- Issued
- Oct 6, 1989
- Abate by
- Oct 9, 1989
- Penalty
- Initial $420 · Current $420
1910.219 E01 I
- Issued
- Oct 6, 1989
- Abate by
- Oct 9, 1989
1910.219 I02
- Issued
- Oct 6, 1989
- Abate by
- Oct 18, 1989
- Penalty
- Initial $350 · Current $350
More inspections in this industry (NAICS 000000)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 107294936.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.