OSHA Inspection: I.S.S. ENERGY, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of I.S.S. ENERGY, INC. in JFK FEDERAL BUILDING, BOSTON, MA 02203 (NAICS 000000). OSHA activity number 107535676.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch I.S.S. Energy, INC. — free Get an email when a new federal OSHA severe-injury report for I.S.S. Energy, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
I.S.S. ENERGY, INC.
Site address
JFK FEDERAL BUILDING
City
BOSTON
State
MA
ZIP
02203
Mailing
175 NORTH HARVARD ST., BOSTON, MA 02134
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
7349
Employees
9
Ownership type
A

13 citations on file for this inspection.

5(a)(1)

Serious Gravity 02 3 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Section 5(a)(1) of the Occupational safety and Health Act of 1970:  The
employer did not furnish employment and place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that,  on October 4, 1991, a
fire began at the roof level of the JFK Federal Building, Boston, MA
and the following conditions existed:
(a) JFK roof level:  The wooden cooling tower located on the roof
was not provided with a sprinkler system as required by NFPA 214
Section 5-1.1, 1988.
One method among other methods to abate the condition is to install a
sprinkler system in the cooling tower area.
(b)  JFK roof level:  The wooden cooling tower located on the roof
was not provided with a heat detection system as required by NFPA
214 Section 5-2.8.2 1988.
One method among methods to abate the conditions is to install a heat
detection system in the cooling tower.
(c)  JFK roof level:  The roof of the building did not have adequate
water pressure and volume of water to properly fight the fire which
took place in the cooling tower area as required by NFPA 14 Section
5-3.1 1984.
One method among other methods to abate the conditions is to install a
fire pump within the building to provide and maintain the water pressure
and volume as neccessary throughout the building.
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

5(a)(1)

Serious Gravity 02 272 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that, the fire door assemblies
were not adequately rated for their use:
(a)  JFK:  The labels on the fire rated doors in stairwells 1
through 7 were painted over preventing the authority having
jurisdiction from determining if the fire rating of the doors were
adequate for their use, as required by NFPA 80 Section 1-5.1 1984.
One method among other methods to abate the condition is to locate the
neccessary documentation which would provide the actual rating of the
fire rated doors in stairwells 1 through 7.
(b)  JFK:  The door frames in stairwells 1 through 7 were not
is the frames had a fire rating adequate for their use as required
by NFPA 80 Section 2-5.1 1984.
One method among other methods to abate the condition is to locate the
neccessary documentation which would indicate that the door frames were
in fact fire rated frames.
(c)  JFK:  The lock and latch sets used on fire rated doors in
stairwells 1 through 7 were not fire rated panic hardward.
One method among other methods to abate the condition is to replace the
existing locks and latch sets with fire rated panic hardward.
(d)  JFK:  The fire rated doors leading to starwells 1 through 7
were not equipped with fire rated panic hardware as required by NFPA
101 Section 8-2.2.2.3 1991.
One method among other methods to abate the condition is to install
panic hardware on the fire rated doors.
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

5(a)(1)

Serious Gravity 02 12 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees in that, employees were exposed
to smoke and fire passing through the unsecured access door(s).
(a)  JFK:  The 4 access doors located between the 1st and 3rd floors
of stairwells 1 and 2, were not equipped with labeled latching
devices as required by NFPA 80 Section 10-1.1 1984.
One method among other methods to abate the conditions is to install
fire rated latching devices.
(b)  JFK:  The 4 access doors located between the 1st and 3rd floors
of stairwells 1 and 2, were not self-latching as required by NFPA
80 Section 10-1.2 1984.
One method among other methods to abate the condition is to install
self-latching devices.
(c)  JFK:  The 4 access doors located between the 1st and 3rd floors
of stairwells 1 and 2, were not self closing as required NFPA 80
Section 10-2-2 1984.
One method among other methods to abate the conditions is to install
door closures on all the access doors.
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

5(a)(1)

Serious Gravity 02 2 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees, in that, employees were exposed
to smoke and fire propagating through hallway(s):
(a)  JFK:  The opposite ends of the horizontal exit located on the
3rd floor between the high and low rise buildings were not equipped
with 1 1/2 hour fire rated automatic or self closing doors to
prevent the spread of smoke and fire from one building to the other
as required by NFPA 101 Section 5-1.3.1 (b) 1988.
One method among other methods to abate the condition is to install
1 1/2 hour fire rated automatic or self closing doors at each end of
the horizontal exit.
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

5(a)(1)

Serious Gravity 02 68 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a place of employment which were
free from recognized hazards that were causing or likely to cause death
or serious physical harm to employees, in that, the signs within the
stairwell enclosures were inadequate:
(a)  JFK:  The existing signs located in stairwells 1 through 7 were
inadequate in that the signs did not indicate the terminus of the
top and bottom of the stairwells and the floor level of exit
discharge.
Also the existing signs were not located 5 feet above the
landing and readily visable when the doors were in the open and
closed positions as required by NFPA 101 Section 5-2.2.6.6 1991.
One method among other methods to abate the condition is to affix
appropriate signs at each floor landing of stairwells 1 through 7.
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

1910.36 B02

Serious Gravity 02 136 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

1910.36 B04

Serious Gravity 02 5 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

1910.36 B06

Serious Gravity 02 12 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

1910.36 D02

Serious Gravity 02 9 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

1910.37 D01

Serious Gravity 02 48 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (2)
  • — I (S) $600.00
  • — Z (S) $600.00

1910.37 K01

Serious Gravity 02 5 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (3)
  • — A (S) $600.00
  • — I (S) $200.00
  • — Z (S) $600.00

1910.37 K02

Serious Gravity 02 4 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $600 · Current $600
Recent events (2)
  • — I (S) $600.00
  • — Z (S) $600.00

1910.157 G01

Serious Gravity 10 9 instances 9 exposed
Issued
Feb 25, 1992
Abate by
Mar 30, 1992
Penalty
Initial $4,500 · Current $4,500
Recent events (2)
  • — I (S) $4500.00
  • — Z (S) $4500.00

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 107535676.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.