OSHA Inspection: ARKANSAS POWER & LIGHT

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of ARKANSAS POWER & LIGHT in LEVY SUBSTATION, 47TH & N. DIVISION, NORTH LITTLE ROCK, AR 72118 (NAICS 000000). OSHA activity number 107704587.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Arkansas Power & Light — free Get an email when a new federal OSHA severe-injury report for Arkansas Power & Light is published. One employer, no account, unsubscribe in one click.
Site address
LEVY SUBSTATION, 47TH & N. DIVISION
City
NORTH LITTLE ROCK
State
AR
ZIP
72118
Mailing
P. O. BOX 551, LITTLE ROCK, AR 72203
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
Yes
Union status
Y
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4911
Employees
36
Ownership type
A

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 1, 1993
Abate by
Mar 9, 1993
Penalty
Initial $5,000 · Current $2,500 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not furnish employment and a  place  of  employment  which
were free from recognized hazards that were causing or likely to  cause
death or serious physical harm to  employees  in  that  employees  were
exposed to:
The employer is not limited to abatement methods suggested by OSHA;
i.e., methods explained are general and may not be effective in all
cases.  Other methods of abatement may be equally or more appropriate.
Ultimate responsibility for determining the most appropriate abatement
method rests with the employer, given its superior knowledge of the
specific conditions on its worksite.
The hazard of contacting live 13.8 KV electrical conductors when
required to climb on top of a LTC substation transformer to
connect the lighting bars near the distribution circuit after
all annual maintenance tests had been completed and before
removing all sources of external power to the transformer.
This condition could be corrected by confirming through tests
that the equipment has been isolated from all sources of energy
before starting to make connection.