NORTH LITTLE ROCK, AR —
OSHA Inspection: ARKANSAS POWER & LIGHT
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of ARKANSAS POWER & LIGHT in LEVY SUBSTATION, 47TH & N. DIVISION, NORTH LITTLE ROCK, AR 72118 (NAICS 000000). OSHA activity number 107704587.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ARKANSAS POWER & LIGHT
- Site address
- LEVY SUBSTATION, 47TH & N. DIVISION
- City
- NORTH LITTLE ROCK
- State
- AR
- ZIP
- 72118
- Mailing
- P. O. BOX 551, LITTLE ROCK, AR 72203
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 36
- Ownership type
- A
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Mar 1, 1993
- Abate by
- Mar 9, 1993
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: The employer is not limited to abatement methods suggested by OSHA; i.e., methods explained are general and may not be effective in all cases. Other methods of abatement may be equally or more appropriate. Ultimate responsibility for determining the most appropriate abatement method rests with the employer, given its superior knowledge of the specific conditions on its worksite. The hazard of contacting live 13.8 KV electrical conductors when required to climb on top of a LTC substation transformer to connect the lighting bars near the distribution circuit after all annual maintenance tests had been completed and before removing all sources of external power to the transformer. This condition could be corrected by confirming through tests that the equipment has been isolated from all sources of energy before starting to make connection.
Recent events (2)
- — I (S) $2500.00
- — Z (S) $5000.00
More inspections at Arkansas Power & Light
View Arkansas Power & Light's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 107704587.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.