SAYREVILLE, NJ ·
OSHA Inspection: O'BRIEN ENVIRONMENTAL ENERGY
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of O'BRIEN ENVIRONMENTAL ENERGY in WASHINGTON RD., SAYREVILLE, NJ 08872 (NAICS 000000). OSHA activity number 108904764.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- O'BRIEN ENVIRONMENTAL ENERGY
- Site address
- WASHINGTON RD.
- City
- SAYREVILLE
- State
- NJ
- ZIP
- 08872
- Mailing
- 225 SO. 8TH ST., PHILADELPHIA, PA 19106
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 2
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 30, 1993
- Abate by
- Jul 30, 1993
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to burns, multiple traumatic injuries and/or death from explosion and fire during the "blow-down" operation on the gas filter/separators (scrubbers), which allowed methane gas to escape and enter the main turbine building: a- Employees opening the drain valve(s) on the gas scrubber(s) and allow methane gas vapors to escape and enter the main turbine building through the drainage system and in-take vents. Among other methods, some feasible and acceptable abatement methods to correct this hazard is: 1- Close off in-take vents located 15' from scrubbers to prevent methane gas from entering the turbine hall during "blow-down". 2- Provide all drains, pipes, and related equipment of the oily/water separator system with traps to prevent any methane gas from re-entering the main turbine hall after the "blow-down" is completed. (See API chapter XVII-1975, Guide for Inspection of Refinery Equipment) 3- Develop written Standard Operating Procedures and train all operators in teh procedures for the "blow-down" operation to prevent natural gas (methane) from escaping from the refinery/gas scrubbers during "blow-down" procedure. (See Manufacturing Chemists Association publication SG-15; API 750-1990, Management of Process Hazards; NFPA 850-1986, Chapter 2 - Administrative Controls)
Recent events (2)
- · F (S) $2500.00
- · Z (S) $5000.00
1910.36 B04
- Issued
- Jun 30, 1993
- Abate by
- Jul 30, 1993
- Penalty
- Initial $2,500 · Current $1,250 Reduced
Recent events (2)
- · F (S) $1250.00
- · Z (S) $2500.00
1910.36 B05
- Issued
- Jun 30, 1993
- Abate by
- Jul 30, 1993
- Penalty
- Initial $2,500 · Current $1,250 Reduced
Recent events (2)
- · F (S) $1250.00
- · Z (S) $2500.00
More inspections in this industry (NAICS 000000)
More inspections in NJ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 108904764.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.