ATLANTA, GA —
OSHA Inspection: METRO ELECTRICAL CONTRACTORS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of METRO ELECTRICAL CONTRACTORS, INC. in THORNE AVENUE & MILLER DRIVE, ATLANTA, GA 30330 (NAICS 000000). OSHA activity number 108964388.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- METRO ELECTRICAL CONTRACTORS, INC.
- Site address
- THORNE AVENUE & MILLER DRIVE
- City
- ATLANTA
- State
- GA
- ZIP
- 30330
- Mailing
- 1263 ELLSWORTH DRIVE, ATLANTA, GA 30318
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 1731
- Employees
- 2
- Ownership type
- A
- Industry flags
- Construction safety.
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 23, 1995
- Abate by
- Jul 6, 1995
- Penalty
- Initial $300 · Current $300
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: confined space entry hazards. (a)Job site - Fort McPherson, GA. Employees enter confined space (electrical vault underground) to perform construction activities, and were exposed to the hazards of oxygen deficiency, toxic substances and flammable/combustible gases. Feasible and acceptable abatement methods to correct this hazard include, but are not limited to: 1) Train employees in the appropriate procedures and controls for confined space entry, emphasizing that entry without the appropriate precautions can be fatal and that their senses are unable too detect and evaluate the severity of atmospheric hazards. 2) Conduct appropriate test for the atmosphere at different levels or heights throughout the space to ensure that the oxygen content is at least 19.5and that flammable/combustible, toxic gases are at safe levels. 3) Use mechanical ventilation to thoroughly ventilate the confined space prior to entry and during the work being performed to ensure that condition are safe. Test the atmosphere in the confined space while working to ensure that condition remain safe. 4) Train employees in the appropriate emergency rescue procedures.
1926.403 B02
- Issued
- Jun 23, 1995
- Abate by
- Jun 28, 1995
More inspections at Metro Electrical Contractors, INC.
View Metro Electrical Contractors, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 108964388.