LONGVIEW, TX ·
OSHA Inspection: COLONY CABINETS INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of COLONY CABINETS INC in 323 RUSSELL DR, LONGVIEW, TX 75602 (NAICS 000000). OSHA activity number 109096487.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COLONY CABINETS INC
- Site address
- 323 RUSSELL DR
- City
- LONGVIEW
- State
- TX
- ZIP
- 75602
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2542
- Employees
- 17
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- May 11, 1995
- Abate by
- Jun 28, 1995
- Penalty
- Initial $1,000 · Current $600 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employmnent and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees when compressed air is transmitted through polyvinyl chloride (PVC) pipe, exposing employees to the hazard of being struck by flying fragments: a.Polyvinyl chloride PVC pipe was installed throughout the plant and used to transmit compressed air to machinery and hand held tools. Feasible abatement methods to correct this condition may include but are not limited to, 1) enclosing the polyvinyl chloride (PVC) line in a conduit pipe of sufficient strength to provide protection form external damage and prevent employees from being struck by flying fragments; 2) install a pipe system designed for compressed air as recommended by the American National Standards Institute/American society of Mechanical Engineers (ANSI/ASME) B31.8-1986 sections 842.32, 842.43 and 849.52 (b) Gas Transmission and Distribution Piping System.
Recent events (2)
- · I (S) $600.00
- · Z (S) $1000.00
1910.147 C01
- Issued
- May 11, 1995
- Abate by
- Jun 28, 1995
- Penalty
- Initial $600 · Current $360 Reduced
Recent events (2)
- · I (S) $360.00
- · Z (S) $600.00