FRACKVILLE, PA —
OSHA Inspection: TRI-M CORPORATION
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of TRI-M CORPORATION in SCI MAHANOY, 301 MOREA ROAD, FRACKVILLE, PA 17931 (NAICS 000000). OSHA activity number 109361287.
Where did this inspection happen?
- Establishment
- TRI-M CORPORATION
- Site address
- SCI MAHANOY, 301 MOREA ROAD
- City
- FRACKVILLE
- State
- PA
- ZIP
- 17931
- Mailing
- 204 GALE LANE, P. O. BOX 69, KENNETT SQUARE, PA 19348
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 1731
- Employees
- 12
- Ownership type
- A
- Industry flags
- Construction safety.
Citations
4 citations on file for this inspection.
5(a)(1)
- Issued
- Aug 26, 1992
- Abate by
- Sep 25, 1992
- Penalty
- Initial $3,500 · Current $2,000 Reduced
General-duty citation text
The alleged violations below have been grouped because they involve similar or related hazards that may increase the potential for injury resulting from an accident. Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to asphyxiation hazards: a) S.C.I. Mahanoy, 301 Morea Road, Frackville, PA jobsite: electrical manhole, location No. 18 electrician assigned to perform work in a manhole was exposed to hazard of asphyxiation in that a permit system and a confined space entry program were not implemented, June 16, 1992. AMONG OTHER METHODS, ONE FEASIBLE AND ACCEPTABLE METHOD TO CORRECT THIS HAZARD IS THE ESTABLISHMENT OF A CONFINED SPACE ENTRY PROGRAM CONSISTING OF AT LEAST THE FOLLOWING: 1. Implementation of confined space entry permit procedures which lists the precautions to be taken. The following "checklist" or precautions should be included on the entry permit: hazard(s) identified; testing and emergency procedures established; electrical equipment de-energized and locked-out; contaminants diluted by purging or ventilation; lifelines and safety belts utilized, and rescue equipment in place and tested. 2. Conduct atmosphere monitoring and testing prior to entry and during the time period that work is being performed in the confined space. Testing shall be for oxygen content and toxic substance concentrations. 3. Attach a safety belt and lifeline to the employee entering the confined space. 4. Provide a trained standby employee outside of the vessel to maintain communication with the confined space workers, unobstructed lifelines, and procedures for obtaining immediate help in the event of an emergency. Rescuers should be instructed and drilled in rescue procedures. Rescuers should be informed not to enter the confined area unless others are standing by in the event that additional help is required. The rescuer should be equipped with proper personal protective equipment including a lifeline and safety belt. 5. Instruct employees as to the nature of the hazards involved and the necessary precautions to be taken in regard to entry into the manhole. Employeesshould be trained with emphasis on the hazards associated with their work, the proper entry procedures to be followed and the required personal protective equipment needed when entry is made. Rescuers should be trained in artificial respiration techniques and basic first-aid procedures. 6. Provide sufficient exhaust ventilation to keep the concentration of toxic substances in the manhole to within permissible exposure limits and ensure that ventilation exhaust ducts discharge clear of working areas. 7. Provide readily available emergency standby equipment consisting of a safety line and/or harness of sufficient length and where the internal atmosphere is oxygen deficient or contains toxic gases, a self-contained breathing apparatus or a supplied-air respirator should be utilized by the employee entering the confined space and one available for rescue. 8. All entrances to confined spaces should be posted: "Danger, confined space, entry by permit only".
Recent events (2)
- — I (S) $2000.00
- — Z (S) $3500.00
1926.20 B02
- Issued
- Aug 26, 1992
- Abate by
- Sep 13, 1992
1926.21 B06 I
- Issued
- Aug 26, 1992
- Abate by
- Sep 13, 1992
1910.333 B02 I
- Issued
- Aug 26, 1992
- Abate by
- Sep 3, 1992
More inspections at Tri-M Corporation
View Tri-M Corporation's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 109361287.