HARTFORD, CT ·
OSHA Inspection: BRAINARD AIRPORT AIR TRAFFIC CONTROL TOWER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BRAINARD AIRPORT AIR TRAFFIC CONTROL TOWER in BRAINARD AIRPORT, HARTFORD, CT 06114 (NAICS 000000). OSHA activity number 109827469.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BRAINARD AIRPORT AIR TRAFFIC CONTROL TOWER
- Site address
- BRAINARD AIRPORT
- City
- HARTFORD
- State
- CT
- ZIP
- 06114
- Mailing
- 12 N.E. EXEC PK,FAA REG HQ, ATTN: N. SMITH,ANE-460, BURLINGTON, MA 01803
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 9621
- Employees
- 11
- Ownership type
- D
Citations
21 citations on file for this inspection.
1910.305 G01 III
- Issued
- Mar 22, 1993
- Abate by
- May 6, 1993
1910.1200 H
- Issued
- Mar 22, 1993
- Abate by
- May 6, 1993
10201 A
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
General-duty citation text
EO 12196 Sec 1-201(a): Fire stopping was not provided around every duct, pipe conduit or other material which passes through a fire resistive wall, partition or floor: IN THE FOLLOWING LOCATIONS, THERE WERE TELEPHONE AND CONTROL WIRES THAT RAN THROUGH FIRE RESISTANCE WALLS AND CEILINGS AND WERE NOT PROVIDED WITH FIRE STOPPING (GROUTING). A. MECHANICAL ROOM, 2ND LEVEL B. STAIRWAY, SECOND LEVEL C. FIRE PARTITIONS DID NOT HAVE A 1-HOUR FIRE RESISTIVE RATING. 1. ATC TOWER STAIRWAY: THE SIDE HINGED SWINGING, SWINGING TYPE DOORS WERE UL LISTED FOR 3/4 HOUR. DOORS WERE INSTALLED FOR FIRE CUTOFF. EXIT DOORS WERE NOT CAPABLE OF OPENING AT LEAST 90 DEGREES: 2. THE EXIT DOORS FROM ROOMS OFF OF STAIRWAY DID NOT OPEN MORE THAN 85-86 DEGREES. PAINTS, VENEER AND OTHER THIN FINAL FINISHING MATERIAL WAS MORE THAN 0.035 INCHES THICK AND THE MATERIAL INCREASED THE FIRE HAZARD RATING OF THE BASE MATERIAL INVOLVED: 3. COMBUSTIBLE PAINT WAS USED TO REFINISH METAL STAIRS AND THE THICKNESS OF PAINT EXCEEDED 0.035 INCH ON SECTIONS OF STAIRS. CARPETING WAS MOUNTED ON WALLS AND CEILING: ATC TOWER: FLOOR CARPETING WAS PLACED ON HALF WALLS.
1904.2 A
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.36 D02
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.37 Q02
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.38 A01
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.38 B03
- Issued
- Mar 19, 1993
- Abate by
- Mar 24, 1993
1910.145 C03
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.151 C
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.157 E03
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.157 G01
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.305 B01
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.305 B02
- Issued
- Mar 19, 1993
- Abate by
- Apr 7, 1993
1910.305 G01 I
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.305 G02 III
- Issued
- Mar 19, 1993
- Abate by
- Mar 24, 1993
1910.333 B02 I
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.1200 E01
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.1200 F05 I
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.1200 F05 II
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
1910.1200 G01
- Issued
- Mar 19, 1993
- Abate by
- May 5, 1993
More inspections in this industry (NAICS 000000)