SHADYSIDE, OH ·
OSHA Inspection: FIRSTENERGY CORP. DBA FIRSTENERGY GENERATION CORP.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of FIRSTENERGY CORP. DBA FIRSTENERGY GENERATION CORP. in 57246 FERRY LANDING ROAD, SHADYSIDE, OH 43947 (NAICS 221112). OSHA activity number 112531215.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FIRSTENERGY CORP. DBA FIRSTENERGY GENERATION CORP.
- Site address
- 57246 FERRY LANDING ROAD
- City
- SHADYSIDE
- State
- OH
- ZIP
- 43947
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221112
- SIC code (legacy)
- 4911
- Employees
- 97
- Ownership type
- A
Citations
8 citations on file for this inspection.
5(a)(1)
- Issued
- Dec 9, 2005
- Abate by
- Jan 11, 2006
- Penalty
- Initial $2,125 · Current $2,125
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that condition assessments, nondestructive examinations, and tube replacements/repairs were not conducted on boiler tubes to minimize the frequency of tube failures and employee exposure to the hazards of steam: a.On or about July 26, 2005, at the First Energy Corp., R.E. Burger Plant site where unit 3, boiler 5 was being operated with 1 ID (induced draft) fan and 2 FD (forced draft) fans, boiler tube #41 ruptured and washed out tube #40 in the furnace rear wall of the waterwall creating an excessive furnace pressure and releasing steam and/or hot gasses into work areas of the plant, thereby causing three contracted employees to receive severe burns. Among other methods, feasible and acceptable abatement methods to correct this hazard include, but are not limited to, the following: 1.Develop a maintenance and equipment inspection program as referenced in Section 4 of NFPA 85, Boiler and Combustion Systems Hazards Code. 2.Conduct a condition assessment and review of historical maintenance records of boiler components and auxiliaries including all boiler tubing such as the steam-carrying tubes, water- carrying tubes, and risers in accordance with Babcock & Wilcox, STEAM its generation and use, 40th EDITION, copyright 1992. 3.Perform nondestructive and/or destructive examinations of boiler tubing to determine the extent of erosion, corrosion, and any other damage in accordance with Babcock & Wilcox, STEAM its generation and use, 40th EDITION, copyright 1992. Examples of nondestructive examinations include, but are not limited to, ultrasonic testing, eddy current, and electromagnetic acoustic transducer. 4.Based on condition assessments and examinations, develop a comprehensive maintenance program and schedule outages for conducting preventative maintenance, testing, and replacement/repair of boiler tubes to minimize tube and other component failure in accordance with Babcock & Wilcox, STEAM its generation and use, 40th EDITION, copyright 1992. 5.Coordinate with EPRI (Electric Power Research Institute) and utilize their "Boiler Life and Availability Improvement Program" to develop tools and techniques to conduct inspections, evaluations, and testing based on the boiler's history and type of tube failures. 6.Conduct an extended life study/health study and schedule outages on unit 3 as performed on units 4 and 5 at First Energy Corp., R.E. Burger Plant.
Recent events (2)
- · F (S) $2125.00
- · Z (S) $2125.00
1910.24 H
- Issued
- Dec 9, 2005
- Abate by
- Mar 18, 2007
- Penalty
- Initial $1,275 · Current $2,000
Recent events (2)
- · F (S) $2000.00
- · Z (S) $1275.00
1910.24 D
- Issued
- Dec 9, 2005
- Abate by
- Mar 18, 2007
Recent events (2)
- · F (S)
- · Z (S)
1910.24 E
- Issued
- Dec 9, 2005
- Abate by
- Mar 18, 2007
Recent events (2)
- · F (S)
- · Z (S)
1910.269 D08 II
- Issued
- Dec 9, 2005
- Abate by
- Apr 7, 2007
- Penalty
- Initial $2,125 · Current $2,000 Reduced
Recent events (2)
- · F (S) $2000.00
- · Z (S) $2125.00
1910.269 D02 IV
- Issued
- Dec 9, 2005
- Abate by
- Apr 7, 2007
Recent events (2)
- · F (S)
- · Z (S)
1910.269 D08 IV
- Issued
- Dec 9, 2005
- Abate by
- Apr 7, 2007
- Penalty
- Initial $2,125 · Current $1,750 Reduced
Recent events (2)
- · F (S) $1750.00
- · Z (S) $2125.00
1910.269 V01 I
- Issued
- Dec 9, 2005
- Abate by
- Apr 7, 2006
- Penalty
- Initial $2,125 · Current $1,250 Reduced
Recent events (2)
- · F (S) $1250.00
- · Z (S) $2125.00
More inspections at Firstenergy Corp. DBA Firstenergy Generation Corp.
View Firstenergy Corp. DBA Firstenergy Generation Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 221112)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 112531215.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.