OSHA Inspection: D & R RADIATOR SERVICE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of D & R RADIATOR SERVICE in 2816 SPRING GROVE AVE., CINCINNATI, OH 45225 (NAICS 000000). OSHA activity number 121980809.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch D & R Radiator Service for free Get an email when a new federal OSHA severe-injury report for D & R Radiator Service is published. One employer, no account, unsubscribe in one click.
Site address
2816 SPRING GROVE AVE.
City
CINCINNATI
State
OH
ZIP
45225
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (N)
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
7539
Employees
4
Ownership type
Private (A)

6 citations on file for this inspection.

5(a)(1)

Serious Gravity 03 1 instance 2 exposed
Issued
May 3, 1999
Abate by
May 13, 1999
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
(a)  Employees were exposed to fire or explosion hazards where natural
gas, the fuel gas used
in conjunction with air from a compressor for soldering operation(s), was
supplied through
flexible copper tubing connected to rubber hose (torch hose) which was
then connected to the
torch. The connection(s) were made by sliding the torch hose over the
copper tubing or the inlet
at the torch without a clamp or other device to secure the connection and
prevent it from
accidently being pulled apart and allowing gas to escape.  Additionally,
manual shut off valves
were not readily accessible in that they were partially blocked by
radiator test tank(s), unused
cylinders, etc.
Among other methods, one feasible and acceptable means for abating this
condition includes
ensuring compliance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
1996, Sections
2.6.9, 3.10 and 5.5.2, respectively, as it applies to the design,
installation and use of pipe,
tubing and fittings to supply natural gas.  Specifically, (1) joint
connections between the tubing
and hose shall be clamped (or secured by other compression-type fittings)
so that the longitudinal
pull-out resistance is equal to the tensile strength of the piping
material (torch hose) and are free
of rough or sharp edges; (2) manual gas shut off valves shall be available
and accessible; and
(3) the connector (torch hose) shall be of minimum length and shall not
exceed 6'.eed

1910.106 E06 I

Serious Gravity 03 2 instances 2 exposed
Issued
May 3, 1999
Abate by
May 6, 1999

1910.106 E06 II

Serious Gravity 03 1 instance 2 exposed
Issued
May 3, 1999
Abate by
May 6, 1999

1910.215 A04

Serious Gravity 02 1 instance 2 exposed
Issued
May 3, 1999
Abate by
May 10, 1999

1910.215 B09

Serious Gravity 02 1 instance 2 exposed
Issued
May 3, 1999
Abate by
May 10, 1999

1910.253 E01

Serious Gravity 03 1 instance 2 exposed
Issued
May 3, 1999
Abate by
May 13, 1999

View D & R Radiator Service's full OSHA safety record →