SHREVEPORT, LA ·
OSHA Inspection: PENNZOIL-QUAKER STATE CO. SHREVEPORT REFINERY
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of PENNZOIL-QUAKER STATE CO. SHREVEPORT REFINERY in 3333 MIDWAY AVE, SHREVEPORT, LA 71109 (NAICS 324110). OSHA activity number 123449480.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PENNZOIL-QUAKER STATE CO. SHREVEPORT REFINERY
- Site address
- 3333 MIDWAY AVE
- City
- SHREVEPORT
- State
- LA
- ZIP
- 71109
- Mailing
- PO BOX 3099, SHREVEPORT, LA 71113
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (Y)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- SIC code (legacy)
- 2911
- Employees
- 329
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Jul 17, 2000
- Abate by
- Jul 18, 2002
- Penalty
- Initial $151,000 · Current $151,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish to each of his employees a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the following condition(s): Pennzoil-Quaker State Company Shreveport Refinery, Naphtha Unifiner, Shreveport LA. For the period of time up to and including 18 Jan 00, Heat exchangers in the Naphtha Unifiner (specifically the 55-EX-02B exchanger) were continually inspected using the inspection criteria set forth in API 510. Corrosion problems have occurred previously. Failure to modify the inspection procedures in light of historical experience exposed employees to the hazards related to failure of the exchanger. Among other methods, one feasible and acceptable abatement method to correct this hazard is to conduct ultrasonic transmission (UT) inspections of the heat exchangers in a way that targeted the expected area of highest concern regarding corrosion and/or vessel failure.
1910.119 C01
- Issued
- Jul 17, 2000
- Abate by
- Jul 18, 2001
1910.119 C02
- Issued
- Jul 17, 2000
- Abate by
- Jul 18, 2001
1910.119 E03 I
- Issued
- Jul 17, 2000
- Abate by
- Oct 20, 2000
1910.119 E03 II
- Issued
- Jul 17, 2000
- Abate by
- Oct 20, 2000
More inspections at Pennzoil-Quaker State CO. Shreveport Refinery
View Pennzoil-Quaker State CO. Shreveport Refinery's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 123449480.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.