HOWARD BEACH, NY ·
OSHA Inspection: CONSOLIDATED EDISON OF NY, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CONSOLIDATED EDISON OF NY, INC. in CROSSBAY BLVD. NO. OF NO. CHANNEL BRIDGE, HOWARD BEACH, NY 11414 (NAICS 000000). OSHA activity number 17674227.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONSOLIDATED EDISON OF NY, INC.
- Site address
- CROSSBAY BLVD. NO. OF NO. CHANNEL BRIDGE
- City
- HOWARD BEACH
- State
- NY
- ZIP
- 11414
- Mailing
- 118 29 QUEENS BLVD, KEW GARDENS, NY 11375
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 2
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Jan 8, 1988
- Abate by
- Jan 11, 1988
- Penalty
- Initial $630 · Current $630
General-duty citation text
Section 5 (a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to: a) On or about 7/30/87 employees were exposed to a "D" fault-fire, possible explosion from 27,000 volts minimum of 17,500 amps on an energized feeder cable. The feeder cable 9B08 located in a manhole at south Channel Bridge, Howard Beach, NY 11414, was not immediately removed from service and repaired as required in Con Edison EO 1184-3 (1/12/98), Distribution Underground Cable Joint Inspections "C" & "D" Faults. Employees were engaged in blanketing the swollen joint in order to work on another feeder cable. Among other methods, one feasible and acceptable abatement method to correct this hazard is: Remove "D" Fault line, do not enter manhole without deenergizing the feeder cable.
Recent events (2)
- · J (S) $630.00
- · Z (S) $630.00
More inspections at Consolidated Edison of NY, INC.