NORTH SMITHFIELD, RI —
OSHA Inspection: LIQUID CARBONICS CORP INC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of LIQUID CARBONICS CORP INC in STEEL STREET, NORTH SMITHFIELD, RI 02895 (NAICS 000000). OSHA activity number 17925579.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LIQUID CARBONICS CORP INC
- Site address
- STEEL STREET
- City
- NORTH SMITHFIELD
- State
- RI
- ZIP
- 02895
- Mailing
- P.O. BOX 67, SLATERSVILLE, RI 02876
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2813
- Employees
- 19
- Ownership type
- A
Citations
25 citations on file for this inspection.
5(a)(1)
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $5,000 · Current $3,750 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees in the calcium carbide storage and charging rooms were exposed to a fire/explosion hazard when calcium carbide containers were allowed to accumulate ice in a nonweather-tight room and adequate precautions were not taken to prevent the possibility of the ice still being present when the containers were opened. If water and calcium carbide were to contact one another, flammable and/or explosive acetylene gas would be accidentally generated in a uncontrolled manner. Among other methods, some feasible and acceptable abatement methods to correct this hazard are the following: 1. To design a closed system; or 2. To assure as far as possible that water/ice does not enter the open system by taking the following steps: a) Fully weather tighten the area in which the calcium carbide is stored; b) Provide adequate heat in both the calcium carbide storage and charging rooms; c) Monitor the calcium carbide storage and charging rooms for moisture content; d) Instruct employees to check all containers for ice and water and to remove all ice and water found prior to bringing any of the containers into the charging area; e) Conduct employee training in the awareness, identification and control of the hazards and instruct employees to not operate the facility if there were to be a water or icing
Recent events (2)
- — F (S) $3750.00
- — Z (S) $5000.00
5(a)(1)
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,500 · Current $2,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees working in the Acetylene Generation Building on or about 02/17/94 were exposed to the hazard of severe burns from wearing clothing made of polyester in an area where there is a possibility of exposure to fire resulting from an accidental release of flammable and/or explosive acetylene gas. This presents a hazard because polyester will melt under extreme heat conditions, increasing the hazard of severe burns to the skin. Among other methods, one feasible and acceptable abatement method to correct this hazard is to provide all employees with clothing which is in compliance with NFPA 1975, such as fire resistant clothing, Proban or Nomex flame resistant
Recent events (2)
- — F (S) $2500.00
- — Z (S) $2500.00
1910.22 D01
- Issued
- Aug 1, 1994
- Abate by
- Jun 30, 1995
- Penalty
- Initial $2,000 · Current $1,500 Reduced
Recent events (3)
- — P (S) $1500.00
- — F (S) $1500.00
- — Z (S) $2000.00
1910.23 A03
- Issued
- Aug 1, 1994
- Abate by
- Aug 4, 1994
- Penalty
- Initial $2,000 · Current $1,500 Reduced
Recent events (2)
- — F (S) $1500.00
- — Z (S) $2000.00
1910.23 A08
- Issued
- Aug 1, 1994
- Abate by
- Aug 25, 1994
- Penalty
- Initial $1,500 · Current $1,125 Reduced
Recent events (2)
- — F (S) $1125.00
- — Z (S) $1500.00
1910.37 G03
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,000 · Current $1,500 Reduced
Recent events (2)
- — F (S) $1500.00
- — Z (S) $2000.00
1910.38 B02
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,500 · Current $1,875 Reduced
Recent events (2)
- — F (S) $1875.00
- — Z (S) $2500.00
1910.102 C
- Issued
- Aug 1, 1994
- Abate by
- Apr 30, 1995
- Penalty
- Initial $5,000 · Current $3,750 Reduced
Recent events (2)
- — F (S) $3750.00
- — Z (S) $5000.00
1910.119 C01
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,500 · Current $1,875 Reduced
Recent events (2)
- — F (S) $1875.00
- — Z (S) $2500.00
1910.119 J02
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
Recent events (2)
- — F (S)
- — Z (S)
1910.119 N
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
Recent events (2)
- — F (S)
- — Z (S)
1910.133 A01
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $1,500 · Current $1,125 Reduced
Recent events (2)
- — F (S) $1125.00
- — Z (S) $1500.00
1910.146 C02
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $7,000 · Current $5,250 Reduced
Recent events (2)
- — F (S) $5250.00
- — Z (S) $7000.00
1910.146 C04
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
Recent events (2)
- — F (S)
- — Z (S)
1910.146 D03
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $7,000 · Current $5,250 Reduced
Recent events (2)
- — F (S) $5250.00
- — Z (S) $7000.00
1910.146 G01
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $7,000 · Current $5,250 Reduced
Recent events (2)
- — F (S) $5250.00
- — Z (S) $7000.00
1910.178 C02 IV
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,500 · Current $1,875 Reduced
Recent events (2)
- — F (S) $1875.00
- — Z (S) $2500.00
1910.219 C02 I
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,000 · Current $1,500 Reduced
Recent events (2)
- — F (S) $1500.00
- — Z (S) $2000.00
1910.219 C04 I
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
Recent events (2)
- — F (S)
- — Z (S)
1910.219 F03
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $2,000 · Current $2,000
Recent events (2)
- — F (S) $2000.00
- — Z (S) $2000.00
1910.305 J04 IIE
- Issued
- Aug 1, 1994
- Abate by
- Aug 4, 1994
- Penalty
- Initial $5,000 · Current $3,750 Reduced
Recent events (2)
- — F (S) $3750.00
- — Z (S) $5000.00
1910.23 C01
- Issued
- Aug 1, 1994
- Abate by
- Aug 4, 1994
- Penalty
- Initial $12,500 · Current $1,875 Reduced
Recent events (2)
- — F (S) $1875.00
- — Z (R) $12500.00
1910.147 C04 I
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
- Penalty
- Initial $12,500 · Current $1,875 Reduced
Recent events (2)
- — F (S) $1875.00
- — Z (R) $12500.00
1910.147 C07 I
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
Recent events (2)
- — F (R)
- — Z (R)
1910.37 K01
- Issued
- Aug 1, 1994
- Abate by
- Jan 30, 1995
Recent events (2)
- — F (O)
- — Z (O)
More inspections in this industry (NAICS 000000)
More inspections in RI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 17925579.