ALBUQUERQUE, NM —
OSHA Inspection: INSULFOAM AKA WESTERN INSULFOAM
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of INSULFOAM AKA WESTERN INSULFOAM in 10010 TRUMBULL AVE.SE, ALBUQUERQUE, NM 87123 (NAICS 000000). OSHA activity number 300048394.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INSULFOAM AKA WESTERN INSULFOAM
- Site address
- 10010 TRUMBULL AVE.SE
- City
- ALBUQUERQUE
- State
- NM
- ZIP
- 87123
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 3086
- Employees
- 18
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
6 citations on file for this inspection.
90005 A
- Issued
- Sep 18, 1997
- Abate by
- Nov 5, 1997
- Penalty
- Initial $1,100
General-duty citation text
Section 50-9-5(A), NMSA 1978 (New Mexico Occupational Health and Safety Act): Every employer shall furnish to each of his employees employment and a place of employment which are free from recognized hazards that are causing or are likely to cause death or serious physical harm to his employees. ASME sections 842.32 and 849.43 and ANSI B31.8-1986 limits the operating pressure of plastic distribution systems to 100 PSI and prohibits the installation of such systems above ground except where "...the above ground portion of the plastic service line is completely enclosed in a conduit or casing of sufficient strength to provide protection from external damage and deterioration." : The service lines used to supply compressed air, at 145 PSI, were made of PVC, a material not designed for this purpose because it shatters upon failure of the material from external damage of physical wear. The piping was not encased to protect the employees, where there are instances in which the employees work as near as three feet from these pipes. One feasible and acceptable abatement method would be to replace the piping with one made of material designed for that purpose or to enclose the PVC pipe within a conduit that would contain the debris in case the PVC pipe fails and shatters.
Recent events (2)
- — F (S)
- — Z (S) $1100.00
1910.22 A01
- Issued
- Sep 18, 1997
- Abate by
- Sep 30, 1997
1910.212 A01
- Issued
- Sep 18, 1997
- Abate by
- Nov 5, 1997
1910.215 A04
- Issued
- Sep 18, 1997
- Abate by
- Oct 22, 1997
1910.305 B01
- Issued
- Sep 18, 1997
- Abate by
- Oct 15, 1997
1910.305 B02
- Issued
- Sep 18, 1997
- Abate by
- Oct 7, 1997
More inspections at Insulfoam AKA Western Insulfoam
View Insulfoam AKA Western Insulfoam's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in NM
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 300048394.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.