OSHA Inspection: BOONE BROTHERS ROOFING, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of BOONE BROTHERS ROOFING, INC. in 10TH AND P ST, LINCOLN, NE 68508 (NAICS 000000). OSHA activity number 300056694.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Boone Brothers Roofing, INC. — free Get an email when a new federal OSHA severe-injury report for Boone Brothers Roofing, INC. is published. One employer, no account, unsubscribe in one click.
Site address
10TH AND P ST
City
LINCOLN
State
NE
ZIP
68508
Mailing
8909 WASHINGTON CIR, OMAHA, NE 68127
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
1761
Employees
6
Ownership type
A
Industry flags
Construction safety.

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 7 exposed
Issued
Dec 10, 1999
Abate by
May 30, 2000
Penalty
Initial $3,000 · Current $2,000 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:
On the Roof at the Construction Site at 10th & P Streets Lincoln, NE - The
employer
did not furnish employment and a place of employment which were free from
recognized
hazards that were causing or likely to cause death or serious physical
harm to employees
in that the employees were exposed to:  The hazard of being burned by or
caught in a
fire on the roof as evidenced by the following instances -
1)  The hazard of being burned by or caught in a fire caused by an asphalt
tar kettle
placed on the roof of the building.  This is  also a violation of NFPA
Section 1105.2.
By having the kettle on the roof the potential for a fire to occur is
greatly increased due
to the location of the heat source to any combustible materials on the
roof.
2)  The kettle was placed on the roof within 20' of the building wall,
combustible
materials on the roof, and a building opening.  This is also a violation
of NFPA 1105.5
which states - "Asphalt kettles shall not be located within 20' of any
combustible
material, combustible building surface or building opening."  The kettle
was placed in
an area in which fell under all of these criteria.
3)  The kettle that was being used to heat the tar being spread on the
roof was not
monitored by an attendant that was within 100 feet of the kettle at all
times during the
operation.  This is a violation of NFPA 1105.6 which states - "An
attendant shall be
within 100 feet of a kettle when the heat source is operating.  Ladders or
similar
obstacles shall not form part of the route between the attendant and the
kettle."  The
attendant was on the other side of the roof with a structure between him
and the kettle
with a winding hallway used as the access.
4)  The company routinely heats the asphalt tar at or above the
manufacturer's
recommended flashpoint of 540 degrees.  Through employees interviews it
was stated,
temperatures of as high as 575 degrees have been noticed in the past.
Once
the tar is
heated above 540 degrees it off gases Hydrogen Sulfide.  Hydrogen Sulfide
has an auto-
ignition point of 500 degrees and is highly flammable.
Among other methods, one feasible and acceptable method to control the
hazard is to:
1)  Utilizing the other kettle in which the company owns that is designed
to pump hot tar
up to the roof from ground level.  It is possible that if the kettle is
being used at another
site, that one of these kettles may have to be rented from a local rental
company.
2)  Having an attendant that is NOT a part of the work crew designated as
the kettle man
to monitor the kettle at all times.  By having this person watching the
kettle at all times,
the hazard of overheating will not be an issue.
3)  Ensuring that the area around the kettle is kept free of all
combustible material and
that the kettle is not positioned within 20' of any building or building
opening.4)  By making it company policy that at no time will the
manufacturer's recommended
temperature be exceeded for any reason.  This will help to ensure that
flash fire are
reduced and kept to a minimum.
Abatement certification and abatement documentation is required for this
violation. The
documentation should include written verification of abatement, applicable
measurements
or monitoring results, and photographs or videos which you believe will be
helpful. The
abatement certification sheet is enclosed with the citations.
Recent events (2)
  • — F (S) $2000.00
  • — Z (S) $3000.00

1910.1200 H02 I

Other-than-serious Gravity 01 1 instance 6 exposed
Issued
Dec 10, 1999
Abate by
May 30, 2000
Penalty
Initial $900 · Current $600 Reduced
Recent events (2)
  • — F (O) $600.00
  • — Z (S) $900.00

1910.1200 H03 I

Other-than-serious Gravity 01 1 instance 6 exposed
Issued
Dec 10, 1999
Abate by
May 30, 2000