OSHA Inspection: LARRY'S BURNER SERVICE

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of LARRY'S BURNER SERVICE in 210 N 10TH, OMAHA, NE 68102 (NAICS 000000). OSHA activity number 300057452.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Larry'S Burner Service for free Get an email when a new federal OSHA severe-injury report for Larry'S Burner Service is published. One employer, no account, unsubscribe in one click.
Site address
210 N 10TH
City
OMAHA
State
NE
ZIP
68102
Mailing
7511 MADISON ST, OMAHA, NE 68127
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (N)
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
7699
Employees
2
Ownership type
Private (A)

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 02 1 instance 3 exposed
Issued
Feb 23, 2000
Abate by
Mar 7, 2000
Penalty
Initial $600 · Current $600
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:
The employer did not furnish a place of employment which was free
from recognized hazards that were likely to cause death or serious
physical harm to employees. Employees were exposed to explosions or
other hazards related to improper boiler maintenance and repair.
a). At the jobsite located at 210 N 10th, Omaha, NE, the
Cleaver Brooks boiler second low water cutoff was bypassed
thereby exposing employees to possible overheating of the
furnace pipes resulting in pipe meltdown and possible boiler
explosion.
Among other methods, feasible and acceptable methods to correct the
hazard include, but are not limited to the following;
a). Follow manufacturers guidelines and make sure a control or
interlock is never bypassed to make a boiler run.
b). Follow manufacturers guidelines and make sure safety and
interlock controls are operational at all times.
Abatement certification is required for this violation. The
abatement certification sheet is enclosed with the citation.