OMAHA, NE ·
OSHA Inspection: LARRY'S BURNER SERVICE
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of LARRY'S BURNER SERVICE in 210 N 10TH, OMAHA, NE 68102 (NAICS 000000). OSHA activity number 300057452.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LARRY'S BURNER SERVICE
- Site address
- 210 N 10TH
- City
- OMAHA
- State
- NE
- ZIP
- 68102
- Mailing
- 7511 MADISON ST, OMAHA, NE 68127
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (N)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 7699
- Employees
- 2
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
5(a)(1)
- Issued
- Feb 23, 2000
- Abate by
- Mar 7, 2000
- Penalty
- Initial $600 · Current $600
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish a place of employment which was free from recognized hazards that were likely to cause death or serious physical harm to employees. Employees were exposed to explosions or other hazards related to improper boiler maintenance and repair. a). At the jobsite located at 210 N 10th, Omaha, NE, the Cleaver Brooks boiler second low water cutoff was bypassed thereby exposing employees to possible overheating of the furnace pipes resulting in pipe meltdown and possible boiler explosion. Among other methods, feasible and acceptable methods to correct the hazard include, but are not limited to the following; a). Follow manufacturers guidelines and make sure a control or interlock is never bypassed to make a boiler run. b). Follow manufacturers guidelines and make sure safety and interlock controls are operational at all times. Abatement certification is required for this violation. The abatement certification sheet is enclosed with the citation.
More inspections in this industry (NAICS 000000)
More inspections in NE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 300057452.