CONNELLSVILLE, PA —
OSHA Inspection: ALLEGHENY POWER
Accident-driven inspection · Safety discipline
At a glance
On , OSHA opened an accident-driven safety inspection of ALLEGHENY POWER in S. 7TH STREET, CONNELLSVILLE, PA 15425 (NAICS 000000). OSHA activity number 300381720.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALLEGHENY POWER
- Site address
- S. 7TH STREET
- City
- CONNELLSVILLE
- State
- PA
- ZIP
- 15425
What kind of inspection was it?
- Inspection type
- Accident-driven (A)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 4911
- Employees
- 4966
- Ownership type
- A
Citations
9 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 4, 1998
- Abate by
- Feb 9, 1998
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees who were exposed to steam, fire and explosion and hazards: (a) Boiler room; Workers who operate, inspect, repair, service and interchange equipment and parts on the three "Titusville" automatically fired natural gas boilers were not properly trained nor were they certified to perform these functions. Among other methods one feasible and acceptable method of abatement is to ensure that workers receive training and education through examination and certification in accordance with the American Petroleum Institute, API 510, and the applicable portions of Sections V, VIII and IX of the latest edition of the American Society of Mechanical Engineers, ASME Code and ANSI NB-23. ABATEMENT DOCUMENTATION IS REQUIRED FOR THIS ITEM
Recent events (2)
- — J (S) $7000.00
- — Z (S) $7000.00
5(a)(1)
- Issued
- Feb 4, 1998
- Abate by
- Feb 9, 1998
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees who were exposed to fire, explosion and steam hazards: (a) Boiler room; There was no documented and implemented quality control system for the three "Titusville" automatically fired natural gas boilers that were converted from oil to natural gas. The control panels were altered with "Wagner" lockout boxes. Equipment and parts such as, the main fuel gas regulators, welding on the steam piping system, repaired combustion chambers, adjusted damper arm linkage for air/fuel ratios were not documented on a quality control and inspection program. Among other methods, one feasible and acceptable means of abatement is to implement a documented quality control program for materials, parts, repairs and inspections as outlined in accordance with API 510. ABATEMENT DOCUMENTATION IS REQUIRED FOR THIS ITEM
Recent events (2)
- — J (S)
- — Z (S)
5(a)(1)
- Issued
- Feb 4, 1998
- Abate by
- Feb 9, 1998
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire, explosion and steam hazards: (a) Boiler room; Preventative maintenance inspections were not conducted on a frequent and periodic basis nor were permanent records maintained on the three "Titusville" automatically fired natural gas boilers that were converted from oil fired. Interchanged equipment and parts, repaired combustion chambers, adjusted air/fuel gas ratios for the main and pilot gas valves, altered control panels, a clogged drip leg and a partially opened hydramotor valve were on the boilers. Among other methods, one feasible and acceptable means of abatement is to initiate a progressive and permanent record system for modifications, alterations, materials, parts, and repairs as outlined in accordance with API 510, ASME CSD-1-1995 and the National Boiler Inspection Code, ANSI NB-23 . ABATEMENT DOCUMENTATION IS REQUIRED FOR THIS ITEM
Recent events (2)
- — J (S)
- — Z (S)
5(a)(1)
- Issued
- Feb 4, 1998
- Abate by
- Feb 9, 1998
- Penalty
- Current $1,800
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm in that employees were exposed to fire, explosion and steam hazards. (a) Boiler Room; The three "Titusville" automatically fired natural gas boilers were being operated with manually operated shutoff valves which could not be identified as "On or Off" nor were these handles permanently attached. Among other methods, one feasible and acceptable means of abatement is to permanently install the handles and clearly mark them to clearly indicate "On/Off" positions in accordance with the American Society of Mechanical Engineers, CSD-1-1995. ABATEMENT DOCUMENTATION IS REQUIRED FOR THIS ITEM
Recent events (2)
- — J (S) $1800.00
- — Z (S)
5(a)(1)
- Issued
- Feb 4, 1998
- Abate by
- Feb 9, 1998
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to; fire, explosion and steam hazards. (a) Boiler Room; The three "Titusville" automatically fired natural gas boilers were being operated with a "Wagner" Lockout Box and the "Wagner" Lockout Box on #1 "Titusville" boiler was not functioning in the manner in which it was designed. These "Wagner" Lockout boxes were not approved by the boiler manufacturer nor by a nationally recognized testing agency. Among one feasible and acceptable method of abatement would be to have a nationally recognized testing agency accept the device for it's intended service in accordance with the manufacturer's guidelines and the code requirements of the American Society of Mechanical Engineers CSD-1-1995. ABATEMENT DOCUMENTATION IS REQUIRED FOR THIS ITEM
Recent events (2)
- — J (S)
- — Z (S)
1910.146 C01
- Issued
- Feb 4, 1998
- Abate by
- Mar 9, 1998
- Penalty
- Initial $3,500 · Current $2,300 Reduced
Recent events (2)
- — J (S) $2300.00
- — Z (S) $3500.00
1910.147 C04 II
- Issued
- Feb 4, 1998
- Abate by
- Mar 9, 1998
- Penalty
- Initial $5,000 · Current $3,500 Reduced
Recent events (2)
- — J (S) $3500.00
- — Z (S) $5000.00
1910.147 C06 I
- Issued
- Feb 4, 1998
- Abate by
- Mar 9, 1998
Recent events (2)
- — J (S)
- — Z (S)
1910.147 C07 IIIA
- Issued
- Feb 4, 1998
- Abate by
- Mar 9, 1998
Recent events (2)
- — J (S)
- — Z (S)
More inspections at Allegheny Power
View Allegheny Power's full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 300381720.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.