OSHA Inspection: CONOCO, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CONOCO, INC. in 1000 S. PINE, PONCA CITY, OK 74603 (NAICS 000000). OSHA activity number 300469764.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Conoco, INC. — free Get an email when a new federal OSHA severe-injury report for Conoco, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
CONOCO, INC.
Site address
1000 S. PINE
City
PONCA CITY
State
OK
ZIP
74603
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
000000
SIC code (legacy)
2911
Employees
2700
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Unclassified Gravity 05 1 instance 8 exposed
Issued
Nov 18, 1996
Abate by
Dec 21, 1996
Penalty
Initial $5,000 · Current $5,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The
employer did not
furnish employment and a place of employment which were free from
recognized hazards
that were causing or likely to cause death or serious physical harm to
employees in that
employees were exposed to the recognized hazard of fire and explosion.
Specifically:
On July 08, 1996 at approximately 8:45 PM at the No. 5 Hydrotreater a 10
inch stainless
steel pipe between heat exchangers X-1103 and X-1100 ruptured releasing
hydrocarbons
causing a fire and explosions. The 10 inch pipe failed as a result of
chloride stress corrosion
cracking and metal fatigue which was caused by the piping not being
properly passivated
during startup activities. Among other methods, one feasible and
acceptable abatement
method to correct this hazard is to passivate all austenitic stainless
steel piping in the No. 5
Hydrotreater using a mixture of soda ash and sodium nitrate. Also, develop
and implement a
program for periodic inspections using the proper testing to detect
chloride stress corrosion
cracking in the No. 5 Hydrotreater and all similar units.
Recent events (2)
  • — I (U) $5000.00
  • — Z (S) $5000.00

1910.119 E03 III

Unclassified Gravity 05 1 instance 8 exposed
Issued
Nov 18, 1996
Abate by
Dec 21, 1996
Penalty
Initial $5,000 · Current $5,000
Recent events (2)
  • — I (U) $5000.00
  • — Z (S) $5000.00

View Conoco, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 300469764.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.