Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: CENTRAL TRANSMISSION CO.

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of CENTRAL TRANSMISSION CO. in NORTH OF PAWNEE ON HWY 18, 5 MI/2 MI W ON HWY 15 &, PAWNEE, OK 74058 (NAICS 000000). OSHA activity number 300472222.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Central Transmission CO. for free Get an email when a new federal OSHA severe-injury report for Central Transmission CO. is published. One employer, no account, unsubscribe in one click.
Site address
NORTH OF PAWNEE ON HWY 18, 5 MI/2 MI W ON HWY 15 &
City
PAWNEE
State
OK
ZIP
74058
Mailing
RT 1, BOX 25, PAWNEE, OK 74058
Inspection type
Accident-driven (A)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
4922
Employees
9
Ownership type
A

2 citations on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 10 exposed
Issued
Jan 27, 1997
Abate by
Mar 1, 1997
Penalty
Initial $5,000 · Current $5,000
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
The condition and/or practice or purging flammable gases at ground level
into the plant
environment, where near by ignition sources existed, created an explosion
and fire hazard for
employees and contractors working at the plant. The operation of blowing
down the lines using
the valve on the separator filled the operating plant area with flammable
gases.
Among other means, one feasible and acceptable abatement method to correct
this hazard is to
pipe the gases to a safe area where they can be burned by means of a flare.
Recent events (2)
  • · I (S) $5000.00
  • · Z (S) $5000.00

1910.119 H02 II

Serious Gravity 10 1 instance 10 exposed
Issued
Jan 27, 1997
Abate by
Mar 15, 1997
Penalty
Initial $5,000 · Current $2,500 Reduced
Recent events (2)
  • · I (S) $2500.00
  • · Z (S) $5000.00

View Central Transmission CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 300472222.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.