LOWELL, MA —
OSHA Inspection: BRADFORD INDUSTRIES, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BRADFORD INDUSTRIES, INC. in 75 ROGERS STREET, LOWELL, MA 01852 (NAICS 000000). OSHA activity number 300545993.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BRADFORD INDUSTRIES, INC.
- Site address
- 75 ROGERS STREET
- City
- LOWELL
- State
- MA
- ZIP
- 01852
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2295
- Employees
- 138
- Ownership type
- A
Citations
46 citations on file for this inspection.
5(a)(1)
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $4,000 · Current $3,000 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire hazards: (a) Location - Ink Room: On or about 10-28-98, a room with connecting walls and doorways to other portions of the building was used primarily for the storage of flammable liquids, but which was also used for dispensing and mixing of Class I flammable liquids. The room was over 1,000 square feet, did not meet the safety requirements of a cut-off room, and did not cut off the dispensing and mixing area from the storage area with construction of adequate fire resistive ratings and contained larger quantities in the room than is considered safe. Among other means, feasible means of abatement would be to reduce the amount of Class I, II, and IIIA flammable/combustible liquids in the room to a combined quantity considered acceptable for safety purposes, move dispensing and mixing operations out of the room into one designed for that purpose, and to provide the following design and construction characteristics to the room: 1. A fire-rated wall between the room and rest of the building; 2. Spill containment to prevent liquid spill from flowing into the connected portion of the building. 3. Liquid-tight wall/floor connection at the wall shared by another portion of the building. 4. Approved self-closing fire door to connecting portion of the building. 5. Make-up air ventilation duct into the room be provided with a fire door or damper 6. Exhausts ducts for the ventilation no more then 12 inches from the floor. 7. An airflow switch in the ventilation connected to an audible alarm for ventilation failure. 8. Class I, Division II, wiring and electrical equipment in the room. (b) Location - Urethane Compound Room/Hot Room: On or about 10-28-98, a room with a connecting wall and doorways to another portion of the building was used primarily for the storage of flammable liquids, but which was also used for dispensing and mixing of Class I flammable liquids. The room was over 1,000 sq ft., did not meet the safety requirements for a cut-off room, and did not cut off the dispensing and mixing area from the storage area with construction of adequate fire resistive ratings and contained larger quantities in the room than is considered safe Also, one separate part of the room was used for storage of flammable liquids undergoing a slow polymerization(hot room).Among other means, feasible means of abatement would be to reduce the amount of Class I, II, and IIIA flammable/combustible liquids in the room to a combined quantity considered acceptable for safety purposes, move dispensing and mixing operations out of the room into one designed for that purpose, move the material undergoing polymerization, and to provide the following design and construction characteristics to the room: 1. Repair the hole in fire-rated wall to revalidate fire rating. 2. Spill containment at loading dock and to outside area. 3. Approved self-closing fire doors to connecting portions of the building. 4. Make-up air ventilation duct into the room be provided with a fire door or damper. 5. Exhaust duct for the ventilation no more than 12 inches from the floor. 6. An airflow switch in the ventilation connected to an audible alarm for ventilation failure. 7. Class I, Division II, wiring and electrical equipment in the room. (c) Location - Basement On or about 10-29-98, Class I flammable liquids in containers were stored in the basement along with Class II and III flammable liquids without adequate sprinklers. Among other means, feasible means of abatement would be to: 1. Remove all class I flammable liquids from the basement; 2. Provide adequate sprinkler protection for class I and II liquids.
Recent events (2)
- — I (S) $3000.00
- — Z (S) $4000.00
5(a)(1)
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fall hazards: (a) Location - C-1 Line: On or about 11-5-98, employees were working from a platform which was elevated by the forks of a powered industrial lift truck and the platform was not secured to the forks and midrails were not provided on the platform. Among other means, feasible means of abatement would be to provide a platform which is securely affixed to the forks of the truck and provided with a full guardrail system which includes both a top and midrail.
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2000.00
1910.23 D01 III
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $1,600 · Current $800 Reduced
Recent events (2)
- — I (S) $800.00
- — Z (S) $1600.00
1910.36 B04
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $4,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $4000.00
1910.36 B08
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,000 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2000.00
1910.37 F02
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $2,000 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2000.00
1910.37 J
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $1,600 · Current $1,600
1910.37 Q01
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,000
Recent events (2)
- — I (O)
- — Z (S) $2000.00
1910.37 Q02
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
Recent events (2)
- — I (O)
- — Z (S)
1910.101 B
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,000 · Current $1,000 Reduced
X1000240
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2000.00
1910.106 D02 II
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $2,000 · Current $2,000
24602590043015600930
1910.106 D03 II
- Issued
- Mar 10, 1999
- Abate by
- Mar 16, 1999
- Penalty
- Initial $1,600 · Current $1,600
13400430
1910.106 E02 IIB2
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,800 · Current $2,800
24600430259015600930
1910.106 E07 IB
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $4,000 · Current $1,500 Reduced
Recent events (2)
- — I (S) $1500.00
- — Z (S) $4000.00
1910.106 E09 III
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $1,600 · Current $1,600
1910.145 C03
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,000
04302460259015600930
Recent events (2)
- — I (O)
- — Z (S) $2000.00
1910.146 D02
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $2,000 · Current $2,000
1910.146 D04 I
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
1910.146 D03
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $2,000 · Current $2,000
1910.146 E01
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $2,000
Recent events (2)
- — I (S)
- — Z (S) $2000.00
1910.146 G01
- Issued
- Mar 10, 1999
- Abate by
- Mar 30, 1999
- Penalty
- Initial $2,000 · Current $2,000
Recent events (2)
- — I (S) $2000.00
- — Z (S) $2000.00
1910.146 K02
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $2,000 · Current $2,000
1910.151 C
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $2,000 · Current $2,000
S22722602310
1910.157 C01
- Issued
- Mar 10, 1999
- Abate by
- Mar 28, 1999
- Penalty
- Initial $2,000 · Current $2,000
1910.176 A
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $2,000 · Current $2,000
1910.176 B
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $2,000 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2000.00
1910.178 C02 IV
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,000 · Current $2,000
24602590043015600930
1910.178 M06
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $2,000 · Current $2,000
1910.212 A01
- Issued
- Mar 10, 1999
- Abate by
- Mar 16, 1999
- Penalty
- Initial $2,800 · Current $2,800
1910.212 A01
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
1910.213 A09
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $2,800 · Current $2,800
1910.213 B03
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $4,000 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $4000.00
1910.242 B
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $1,600 · Current $1,600
1910.243 B02
- Issued
- Mar 10, 1999
- Abate by
- Mar 18, 1999
- Penalty
- Initial $2,800 · Current $1,400 Reduced
Recent events (2)
- — I (S) $1400.00
- — Z (S) $2800.00
1910.303 B02
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
- Penalty
- Initial $2,000 · Current $1,000 Reduced
Recent events (2)
- — I (S) $1000.00
- — Z (S) $2000.00
1910.303 E
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $1,200
Recent events (2)
- — I (O)
- — Z (S) $1200.00
1910.303 E
- Issued
- Mar 10, 1999
- Abate by
- Jun 1, 1999
Recent events (2)
- — I (O)
- — Z (S)
1910.303 F
- Issued
- Mar 10, 1999
- Abate by
- Jun 1, 1999
- Penalty
- Initial $1,200 · Current $600 Reduced
Recent events (2)
- — I (S) $600.00
- — Z (S) $1200.00
1910.303 G01 II
- Issued
- Mar 10, 1999
- Abate by
- Mar 16, 1999
- Penalty
- Initial $4,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $4000.00
1910.303 G02 I
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $4,000 · Current $2,000 Reduced
Recent events (2)
- — I (S) $2000.00
- — Z (S) $4000.00
1910.305 B01
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
1910.305 B01
- Issued
- Mar 10, 1999
- Abate by
- Mar 16, 1999
1910.305 B02
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
1910.305 B02
- Issued
- Mar 10, 1999
- Abate by
- Mar 15, 1999
1910.305 D
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
1910.305 G01 III
- Issued
- Mar 10, 1999
- Abate by
- Mar 14, 1999
- Penalty
- Initial $1,600 · Current $800 Reduced
Recent events (2)
- — I (S) $800.00
- — Z (S) $1600.00
More inspections at Bradford Industries, INC.
View Bradford Industries, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 000000)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 300545993.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.