BILLERICA, MA —
OSHA Inspection: TRANS-MATE PRODUCTS, INC.
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of TRANS-MATE PRODUCTS, INC. in 13 STERLING ROAD, BILLERICA, MA 01862 (NAICS 000000). OSHA activity number 300547569.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TRANS-MATE PRODUCTS, INC.
- Site address
- 13 STERLING ROAD
- City
- BILLERICA
- State
- MA
- ZIP
- 01862
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2842
- Employees
- 15
- Ownership type
- A
Citations
4 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 14, 2000
- Abate by
- May 17, 2000
- Penalty
- Initial $375 · Current $375
156022702037T3061060
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards created by storing of excess quantities of flammable liquids adjacent to production: (a) Flammables Storage Area: On or about 8/19/99, an open area for storage of approximately 1500 gallons of flammable liquids was exposed to potential ignition sources in production. Among other methods, feasible means of abatement would be to enclose the area and provide the following design and construction characteristics to the room: 1. A fire-rated wall(s) between the room and rest of the building. 2. Spill containment to prevent liquid spill from flowing into the connected portion of the building. 3. Liquid-tight wall & floor connection(s) at the wall shared by another portion of the building. 4. Approved self-closing fire door to connecting portion of the building. 5. Make-up air ventilation duct into the room be provided with a fire door/damper. 6. Exhaust ducts for ventilation no more than 12 inches from the floor. 7. An airflow switch in the ventilation connected to an audible alarm for ventilation failure. 8. Class I, Division II, wiring and electrical equipment in the room.
1910.23 C01
- Issued
- Feb 14, 2000
- Abate by
- Mar 3, 2000
- Penalty
- Initial $375 · Current $375
1910.1200 F05 I
- Issued
- Feb 14, 2000
- Abate by
- Feb 18, 2000
- Penalty
- Initial $375 · Current $375
D1752260
1910.1200 F05 II
- Issued
- Feb 14, 2000
- Abate by
- Feb 18, 2000
D1752260
More inspections in this industry (NAICS 000000)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 300547569.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.