OSHA Inspection: MARON ELECTRIC COMPANY

Accident-driven inspection · Safety discipline

On , OSHA opened an accident-driven safety inspection of MARON ELECTRIC COMPANY in 101 NORTHWEST POINT BLVD., ELK GROVE VILLAGE, IL 60007 (NAICS 000000). OSHA activity number 300947793.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Maron Electric Company for free Get an email when a new federal OSHA severe-injury report for Maron Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
101 NORTHWEST POINT BLVD.
City
ELK GROVE VILLAGE
State
IL
ZIP
60007
Mailing
5401 W. FARGO, SKOKIE, IL 60077
Inspection type
Accident-driven (A)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (Y)
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
1731
Employees
4
Ownership type
Private (A)

1 citation on file for this inspection.

5(a)(1)

Serious Gravity 10 1 instance 4 exposed
Issued
May 6, 1997
Abate by
May 9, 1997
Penalty
Initial $3,500 · Current $2,500 Reduced
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
On November 16, 1996, four workers under the supervision of Maron Electric
Company and
Power Contracting and Engineering Corporation physically moved a piece of
electrical
equipment, weighing approximately one and one-half tons, over the access
panels of a raised
floor that had been partially dismantled.  The workers were exposed to the
hazard of being
struck by the electrical equipment falling to the subfloor when the raised
floor collapsed.
Among other methods, one feasible and acceptable abatement method to
correct
this hazard would have been to:
Prior to the movement of material or equipment across a raised floor,
determine
the heaviest object that may be moved across the floor, and the manner in
which
it can be safely moved, that will not result in a structural failure of
the raised
floor.  This may be accomplished by, but not limited to, one or more of the
following:
(1) A review of the existing raised floor plan and specifications by
a competent person;
(2) Consultation with the raised floor manufacturer, distributor,
installer, or other competent person;
(3) Evaluation by a registered professional engineer.nal