OSHA Inspection: WORTHINGTON CUSTOM PLASTICS, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of WORTHINGTON CUSTOM PLASTICS, INC. in 4219 NORTH SR 42, MASON, OH 45040 (NAICS 000000). OSHA activity number 301430518.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Worthington Custom Plastics, INC. — free Get an email when a new federal OSHA severe-injury report for Worthington Custom Plastics, INC. is published. One employer, no account, unsubscribe in one click.
Site address
4219 NORTH SR 42
City
MASON
State
OH
ZIP
45040
Mailing
4219 U.S. ROUTE 42, MASON, OH 45040
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Data loaded
NAICS code
000000
SIC code (legacy)
3021
Employees
621
Ownership type
A

2 citations on file for this inspection.

1910.23 C01

Other-than-serious Gravity 10 1 instance 4 exposed
Issued
Jun 25, 1997
Abate by
Aug 12, 1997
Penalty
Initial $5,950
Recent events (2)
  • — F (O)
  • — Z (S) $5950.00

5(a)(1)

Deleted Serious Gravity 10 1 instance 10 exposed
Issued
Jun 25, 1997
Abate by
Jul 22, 1997
Penalty
Initial $5,950 · Current $5,950
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees in that employees
were exposed to:
a) Employees were exposed to excessive levels of Legionella Pneumophila
and Legionella
Species in water sprays or mists during injection mold setting and
changing operations; parts
testing and related activities in the Quality Laboratory; and equipment
repair or preventative
maintenance. Exposure to these contaminated water sprays and mists could
have caused
Legionellosis including Legionnaires' disease or Pontiac fever. Water
samples collected on
March 5 and 13, 1997, analyzed by polymerase chain reaction (PCR)
indicated
organisms per
milliliter (opm) results as follows:
DATELOCATIONLEGIONELLA
PNEUMOPHILIA
Organisms Per
Milliliter (opm)
LEGIONELLA
SPECIES
(opm)3/5/97Return side of Press #43
(chilled water west)> 1000 opm
estimated (est.)
at 1200 > 1000 opm
est. at 1500
3/5/97Gage tap of the output of chilled
water generator; (chilled water east)est. at 1000 opm>1000 opm
est. at 20003/5/97Inlet to the tank of the cooling tower
east.< 1000 opm
est. at 300 > 1000 opm
est. at 12003/5/97In the sump for the water wash paint
booths.None detected> 1000 opm
est. at 45003/5/97Bag filter for the east press  cooling
water.< 1000 opm
est. at 100> 1000 opm
est. at 15003/5/97Return side of Press # 19
(chilled water east)< 1000 opm
est. at 10 > 1000 opm
est. at 15003/5/97In the west cooling tower tank< 1000 opm
est. at 10 > 1000 opm
est. at 30003/5/97Chilled water west storage tank< 1000 opm
est. at 250 < 1000 opm
est. at 8003/13/97Atlas humidity tankNone detected
> 1000 opm
est. at 12003/13/97Evaporative humidifier in the QC
laboratoryNone detectedest. at 1000 opm
Abatement of the water systems to control the levels of Legionella
bacteria and minimize employees'
exposure to water sprays and mists include the following:
1) maintain the cleanliness of the system and the water in it; including
effective water filtration systems
and periodic cleaning and disinfection of holding tanks and reservoirs;
2) use effective water treatment techniques; including use of biocides,
scale removers and corrosion
inhibitors, and maintain appropriate pH levels for the treatment selected;
3) avoid water stagnation by assuring circulation through "dead legs" and
draining unused water systems;
4) avoid water temperatures and conditions that favor the proliferation of
legionella and other micro-
organisms; maintain domestic water heaters at 140 degrees fahrenheit and
water delivered at the faucet
at a minimum of 122 degrees fahrenheit, whenever possible, maintain stored
water below 68 degrees
fahrenheit and above 122 degrees fahrenheit;
5) inspect circulating water systems and holding tanks at least monthly
for leaks and cleanliness;
6) document operation and maintenance of water systems, including water
treatments, pH levels and
mechanical cleaners;
7) test water systems to assure Legionella levels are not elevated and
water maintenance and treatment
is effective;
8) minimize aerosolization of water in operations, whenever possible;
establish and maintain mold
changing and parts testing procedures;
9) train employees on potential sources of exposure to Legionella, routes
of exposure, hazards associated
with exposure to Legionella, and signs and symptoms of Legionnaires'
disease and Pontiac fever.
Recent events (2)
  • — F (S) $5950.00
  • — Z (S) $5950.00

View Worthington Custom Plastics, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 301430518.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.