Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,473Inspections Most recent open 2026-07-28 Last loaded 2026-07-31

OSHA Inspection: SARTOMER COMPANY, INC. (WEST CHESTER PLANT)

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SARTOMER COMPANY, INC. (WEST CHESTER PLANT) in 610 SOUTH BOLMAR STREET, WEST CHESTER, PA 19382 (NAICS 000000). OSHA activity number 301452066.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sartomer Company, INC. (West Chester Plant) for free Get an email when a new federal OSHA severe-injury report for Sartomer Company, INC. (West Chester Plant) is published. One employer, no account, unsubscribe in one click.
Site address
610 SOUTH BOLMAR STREET
City
WEST CHESTER
State
PA
ZIP
19382
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
Yes
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
000000
SIC code (legacy)
2816
Employees
100
Ownership type
A
Industry flags
Manufacturing safety.

5 citations on file for this inspection.

5(a)(1)

Serious Gravity 02 1 instance 20 exposed
Issued
Jun 23, 1999
Abate by
Apr 1, 2000
Penalty
Initial $1,500 · Current $1,500
Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The
employer did not
furnish employment and a place of employment which were free from
recognized hazards that
were causing or likely to cause death or serious physical harm to
employees
in that employees
were exposed to hazards of fire and explosion at Pad C. The following
conditions contributed
to the existence of this hazard:
a)  The inert gas system was not equipped with a means to allow operations
or
maintenance personnel to monitor the status or condition of the system on
an individual
vessel or tank. Operating procedures had not been developed for the
operation of the
inert gas system servicing the Pad C solvent tanks.  The standard
operating procedures
for the recycling of Tank 219 was incomplete, in that it did not address
temporary
conditions such as extended recycle times that may result from
environmental,
production, or other causes.  Piping inspection program for flammable and
combustible
liquids piping at the Pad C area was inadequate.
Abatement Note:Feasible abatement for this item would include the
following.
Other abatement steps may also be acceptable.
Develop and implement the means to allow operations and
maintenance personnel to monitor the status of the inert gas system
on individual tanks.
Procedures and information addressing the operation of the inert
gas system should include how the system functions at Pad C
including a description of all system components; operating
parameters; consequences of deviation from specifications; and
steps to avoid or correct deviations.
Procedures should be developed for recycle times for Tank 219 not
addressed by operating instruction in effect on January 2nd, 1999.
Procedures should be developed for reviewing delays in completion
and implementation of Corrective Action Report items.
A piping inspection program should be developed and implemented
in accordance with API 570 specifications.
Recent events (2)
  • · I (S) $1500.00
  • · Z (S) $1500.00

1910.106 B02 VIIIE

Deleted Serious Gravity 02 1 instance 20 exposed
Issued
Jun 23, 1999
Abate by
Aug 25, 1999
Penalty
Initial $1,500
Recent events (2)
  • · I (S)
  • · Z (S) $1500.00

1910.106 B06

Deleted Serious Gravity 02 1 instance 20 exposed
Issued
Jun 23, 1999
Abate by
Aug 25, 1999
Penalty
Initial $1,500
Recent events (2)
  • · I (S)
  • · Z (S) $1500.00

1910.106 B02 VIIIE

Serious Gravity 03 1 instance 20 exposed
Issued
Jun 23, 1999
Abate by
Apr 1, 2000
Penalty
Initial $2,500 · Current $2,500
Recent events (2)
  • · I (S) $2500.00
  • · Z (S) $2500.00

1910.106 B06

Serious Gravity 01 1 instance 20 exposed
Issued
Jun 23, 1999
Abate by
Apr 1, 2000
Recent events (2)
  • · I (S)
  • · Z (S)

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 301452066.