WEST CHESTER, PA ·
OSHA Inspection: SARTOMER COMPANY, INC. (WEST CHESTER PLANT)
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SARTOMER COMPANY, INC. (WEST CHESTER PLANT) in 610 SOUTH BOLMAR STREET, WEST CHESTER, PA 19382 (NAICS 000000). OSHA activity number 301452066.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SARTOMER COMPANY, INC. (WEST CHESTER PLANT)
- Site address
- 610 SOUTH BOLMAR STREET
- City
- WEST CHESTER
- State
- PA
- ZIP
- 19382
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 000000
- SIC code (legacy)
- 2816
- Employees
- 100
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
5 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 23, 1999
- Abate by
- Apr 1, 2000
- Penalty
- Initial $1,500 · Current $1,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to hazards of fire and explosion at Pad C. The following conditions contributed to the existence of this hazard: a) The inert gas system was not equipped with a means to allow operations or maintenance personnel to monitor the status or condition of the system on an individual vessel or tank. Operating procedures had not been developed for the operation of the inert gas system servicing the Pad C solvent tanks. The standard operating procedures for the recycling of Tank 219 was incomplete, in that it did not address temporary conditions such as extended recycle times that may result from environmental, production, or other causes. Piping inspection program for flammable and combustible liquids piping at the Pad C area was inadequate. Abatement Note:Feasible abatement for this item would include the following. Other abatement steps may also be acceptable. Develop and implement the means to allow operations and maintenance personnel to monitor the status of the inert gas system on individual tanks. Procedures and information addressing the operation of the inert gas system should include how the system functions at Pad C including a description of all system components; operating parameters; consequences of deviation from specifications; and steps to avoid or correct deviations. Procedures should be developed for recycle times for Tank 219 not addressed by operating instruction in effect on January 2nd, 1999. Procedures should be developed for reviewing delays in completion and implementation of Corrective Action Report items. A piping inspection program should be developed and implemented in accordance with API 570 specifications.
Recent events (2)
- · I (S) $1500.00
- · Z (S) $1500.00
1910.106 B02 VIIIE
- Issued
- Jun 23, 1999
- Abate by
- Aug 25, 1999
- Penalty
- Initial $1,500
Recent events (2)
- · I (S)
- · Z (S) $1500.00
1910.106 B06
- Issued
- Jun 23, 1999
- Abate by
- Aug 25, 1999
- Penalty
- Initial $1,500
Recent events (2)
- · I (S)
- · Z (S) $1500.00
1910.106 B02 VIIIE
- Issued
- Jun 23, 1999
- Abate by
- Apr 1, 2000
- Penalty
- Initial $2,500 · Current $2,500
Recent events (2)
- · I (S) $2500.00
- · Z (S) $2500.00
1910.106 B06
- Issued
- Jun 23, 1999
- Abate by
- Apr 1, 2000
Recent events (2)
- · I (S)
- · Z (S)
More inspections in this industry (NAICS 000000)